Benchmark Platinum-Edge [ii]: Operation-Service Manual
SECTION 4 – INITIAL START-UP
PROPANE Combustion Calibration Instructions
Enter the Flame Strength, NOx and CO readings from the Combustion Analyzer
and multi-meter in the Manual Combustion Calibration screen's Reading column.
Enter the same values, plus the O
provided with the unit.
24. Lower the Valve Position to the next calibration point using the  (Left) arrow key (if using
Method 1 in step 11) or the Fine Valve Position – (Minus) key (if using Method 2).
BMK750P & 1000P
BMK1500/2000/2500 DF & P
BMK3000 DF & P
BMK4000 DF & P
BMK5000N DF & P
BMK5000P & 6000P
BMK5000DF & 6000DF
25. Repeat step 17, 18 and 21 at that valve position and the rest of the valve positions in the
Table corresponding to your model. The O
shown in these tables.
TABLE 4-6a: PROPANE Final Valve Positions: BMK750 – 5000N
Valve Position
Oxygen (O
BMK750/1000 SINGLE Fuel
80%
5.5% ± 0.2%
60%
5.5% ± 0.2%
45%
5.5% ± 0.2%
30%
6.3% ± 0.2%
18%
5.5% ± 0.2%
BMK750/1000 DUEL Fuel
70%
5.5% ± 0.2%
50%
5.5% ± 0.2%
40%
5.5% ± 0.2%
30%
5.5% ± 0.2%
18%
5.5% ± 0.2%
BMK1500
70%
5.2% ± 0.2%
50%
5.3% ± 0.2%
40%
6.2% ± 0.2%
30%
7.0% ± 0.2%
18%
8.5% ± 0.2%
OMM-0137_J •
12/20/2022
value, on the Combustion Calibration Data Sheet
2
80%
70%
85%
70%
70%
70%
85%
, NOx and CO should stay within the ranges
2
) %
Nitrogen oxide (NOx)
2
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Carbon Monoxide (CO)
<150 ppm
<150 ppm
<150 ppm
<100 ppm
<100 ppm
<150 ppm
<150 ppm
<150 ppm
<100 ppm
<100 ppm
<150 ppm
<150 ppm
<150 ppm
<100 ppm
<100 ppm