Benchmark Platinum-Edge [ii]: Operation-Service Manual
SECTION 4 – INITIAL START-UP
NATURAL GAS Manual Combustion Calibration Instructions
PRE-SET CALIBRATION CONTROLS
PRESET CALIBRATION POINTS METHOD
Figure 4-6: Manual Combustion Calibration Screens
12. Set the Controller's Enable/Disable switch to Enable.
13. Change the valve position to 30%, press the Go button, then verify that the unit has ignited
and is operating as expected.
14. Use the  (Right) arrow key to change the valve position to 100%, then press Go.
15. Verify that the manifold gas pressure on the downstream side of the SSOV is within the
range shown in Table 4-1. If it isn't, remove the brass hex nut on the SSOV actuator to
access the gas pressure adjustment screw (Figure 4-3). Make adjustments using a flat-tip
screwdriver, slowly rotating the gas pressure adjustment (in 1/4-turn increments)
clockwise to increase gas pressure or counterclockwise to reduce it. The resulting gas
pressure reading on the downstream manometer should fall in the range listed below.
TABLE 4-1: REFERENCE Natural Gas Manifold Gas Pressure Range @ 100%
Fire Rate
Model
BMK750
BMK1000
BMK1500
BMK2000
BMK2500
BMK3000
BMK4000
BMK5000N
BMK5000
BMK5000
(Low Gas Pressure)
BMK6000
BMK6000
(Low Gas Pressure)
* This column lists natural gas pressures on dual fuel units. For propane values, see Section 4.5.2.
NOTE 1: For BMK750 Dual Fuel, measure Natural Gas Manifold Pressure at 80% Fire Rate. Range
shall be 5.0" +/- 0.2" W.C. (1.24 ± 0.05 kPa).
OMM-0137_J •
12/20/2022
Single Fuel Units
2.0" ± 0.2" W.C. (0.50 ± 0.05 kPa)
2.4" ± 0.4" W.C. (0.60 ± 0.10 kPa)
3.6" ± 0.1" W.C. (0.90 ± 0.02 kPa)
3.4" ± 0.2" W.C. (0.85 ± 0.05 kPa)
2.0" ± 0.1" W.C. (0.50 ± 0.02 kPa)
2.1" ± 0.2" W.C. (0.52 ± 0.05 kPa)
3.0" ± 0.2" W.C. (0.75 ± 0.05 kPa)
1.8" ± 0.2" W.C. (0.45 ± 0.05 kPa)
6.3" ± 0.2" W.C. (1.56 ± 0.05 kPa)
2.6" ± 0.2" W.C. (0.65 ± 0.02 kPa)
7.9" ± 0.2" W.C. (1.97 ± 0.05 kPa)
1.9" ± 0.2" W.C. (0.50 ± 0.05 kPa)
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
FINE VALVE POSITION CONTROLS
FINE VP STEP METHOD
Dual Fuel Units *
See NOTE 1
4.9" ± 0.2" W.C. (1.22 ± 0.05 kPa)
3.6" ± 0.1" W.C. (0.90 ± 0.02 kPa)
6.3" ± 0.1" W.C. (1.57 ± 0.02 kPa)
5.8" ± 0.1" W.C. (1.44 ± 0.02 kPa)
6.0" ± 0.2" W.C. (1.49 ± 0.05 kPa)
4.9" ± 0.2" W.C. (1.22 ± 0.05 kPa)
4.9" ± 0.2" W.C. (1.22 ± 0.05 kPa)
6.3" ± 0.2" W.C. (1.57 ± 0.05 kPa)
N/A
7.9" ± 0.2" W.C. (1.97 ± 0.05 kPa)
N/A