Watts AERCO Benchmark BMK5000 Operation And Service Manual page 125

Platinum boilers with edge controller
Hide thumbs Also See for AERCO Benchmark BMK5000:
Table of Contents

Advertisement

Benchmark Platinum-Edge [ii]: Operation-Service Manual
SECTION 9 – AERTRIM OPERATION
BMK3000 AERtrim Values
MENU ITEM
Settle Time
Trim Gain
Max Tries
14%
O
Target
2
30%
40%
(must be
between
50%
O
Upper &
2
70%
O
Lower)
2
100%
14%
O
Lower
2
30%
40%
(must be at
least 1%
50%
lower than
70%
O
Upper)
2
100%
14%
O
Upper
2
30%
40%
(must be at
least 1%
50%
higher than
70%
O
Lower)
2
100%
O
Offset
2
BMK3000 AERtrim Adjustment Range
CALIBRATION POINT
14%
30%
40%
50%
70%
100%
OMM-0137_J •
12/20/2022
Minimum
Maximum
0
120 Sec
0.1
5.0
0
100
3%
8%
3%
8%
3%
8%
3%
8%
3%
8%
3%
8%
2.5%
5.5%
2.5%
5.5%
2.5%
5.5%
2.5%
5.5%
2.5%
5.5%
2.5%
5.5%
5.5%
8.5%
5.5%
8.5%
5.5%
8.5%
5.5%
8.5%
5.5%
8.5%
5.5%
8.5%
-3.0
3.0
BLOWER VOLTAGE
Minimum
Maximum
2.60
4.90
3.60
7.00
4.60
8.00
5.00
9.20
6.10
10.00
7.60
10.00
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Default
20 Sec
0.250
15
6.5%
7.3%
7.5%
7.0%
5.5%
5.0%
5.5%
5.5%
5.5%
5.5%
5.0%
4.5%
7.0%
7.8%
8.0%
7.5%
6.0%
5.5%
1.0
Default
2.80
4.60
5.00
5.50
6.90
9.10
Page 125 of 167

Advertisement

Table of Contents
loading

Table of Contents