Watts AERCO Benchmark BMK5000 Operation And Service Manual page 122

Platinum boilers with edge controller
Hide thumbs Also See for AERCO Benchmark BMK5000:
Table of Contents

Advertisement

Benchmark Platinum-Edge [ii]: Operation-Service Manual
SECTION 9 – AERTRIM OPERATION
BMK1500 AERtrim Values
MENU ITEM
Settle Time
Trim Gain
Max Tries
16%
O
Target
2
30%
40%
(must be
between O
50%
2
Upper & O
2
70%
Lower)
100%
16%
O
Lower
2
Limit
30%
40%
(must be at
50%
least 1%
70%
lower than
O
Upper)
100%
2
16%
O
Upper
2
Limit
30%
40%
(must be at
50%
least 1%
70%
higher than
O
Lower)
100%
2
O
Offset
2
BMK1500 AERtrim Adjustment Range
CALIBRATION POINT
16%
30%
40%
50%
70%
100%
OMM-0137_J •
12/20/2022
Minimum
Maximum
0
120 Sec
0.1
5.0
0
100
3%
8%
3%
8%
3%
8%
3%
8%
3%
8%
3%
8%
2.5%
5.5%
2.5%
5.5%
2.5%
5.5%
2.5%
5.5%
2.5%
5.5%
2.5%
5.5%
5.5%
8.5%
5.5%
8.5%
5.5%
8.5%
5.5%
8.5%
5.5%
8.5%
5.5%
8.5%
-3.0
3.0
BLOWER VOLTAGE
Minimum
Maximum
1.40
3.30
1.90
4.60
2.30
5.70
2.50
5.70
2.70
6.30
6.00
10.00
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Default
20 Sec
0.250
15
5.5%
6.5%
6.5%
6.5%
6.0%
5.0%
5.0%
5.0%
5.0%
5.0%
5.0%
4.5%
6.0%
7.0%
7.0%
7.0%
6.5%
5.5%
1.0
Default
1.80
2.30
2.50
2.90
3.80
7.90
Page 122 of 167