Benchmark Platinum-Edge [ii]: Operation-Service Manual
SECTION 5 – SAFETY DEVICE TESTING
HIGH Gas Pressure Test Instructions: BMK750 – 2500
14. Upon test completion, close the ball valve and remove the manometer. Replace the 1/4"
NPT plug removed in step 2.
MANUAL SHUT-OFF
VALVE
(P/N 22322 shown)
GAS INLET
HIGH GAS PRESSURE
Figure 5-3a: BMK750/1000 HIGH Gas Pressure Test Components
MANUAL
SHUT-OFF
VALVE
(P/N 22314 shown)
HIGH GAS BALL VALVE
Figure 5-3b: BMK1500/2000: HIGH Gas Pressure Fault Test
1/4" NPT
PLUG
OMM-0137_J •
12/20/2022
(install
manometer
BALL VALVE
TO
AIR/FUEL
VALVE
SSOV
HIGH GAS PRESSURE
SWITCH
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
TO AIR/FUEL
VALVE
HIGH GAS
PRESSURE SWITCH
LOW GAS
PRESSURE SWITCH
SSOV
1/4" NTP PLUG
(Install manometer here
for High Gas Pressure
Test)
NATURAL GAS
INLET
HIGH GAS
PRESSURE
SWITCH
LOW GAS
PRESSURE
SWITCH
1/4" NPT PLUG
(Install manometer here
for HIGH gas pressure
fault test)
NATURAL
GAS INLET
Page 66 of 167