Benchmark Platinum-Edge [ii]: Operation-Service Manual
SECTION 4 – INITIAL START-UP
PROPANE Combustion Calibration Instructions
Valve Position
Oxygen (O
BMK2000
70%
6.5% ± 0.2%
50%
6.5% ± 0.2%
40%
6.5% ± 0.2%
30%
6.5% ± 0.2%
18%
5.5% ± 0.2%
BMK2500
70%
5.4% ± 0.2%
45%
5.6% ± 0.2%
30%
6.0% ± 0.2%
22%
5.8% ± 0.2%
18%
6.0% ± 0.2%
BMK3000
85%
5.2% ± 0.2%
65%
5.4% ± 0.2%
45%
6.0% ± 0.2%
30%
6.4% ± 0.2%
18%
6.4% ± 0.2%
BMK4000
70%
4.5% ± 0.2%
50%
5.5% ± 0.2%
40%
5.5% ± 0.2%
30%
5.5% ± 0.2%
18%
5.5% ± 0.2%
BMK5000N
70%
4.5% ± 0.2%
50%
5.5% ± 0.2%
40%
5.5% ± 0.2%
30%
5.5% ± 0.2%
18%
5.5% ± 0.2%
OMM-0137_J •
12/20/2022
) %
Nitrogen Oxide (NOx)
2
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
<100 ppm
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Carbon Monoxide (CO)
<150 ppm
<150 ppm
<150 ppm
<100 ppm
<100 ppm
<150 ppm
<150 ppm
<100 ppm
<100 ppm
<100 ppm
<150 ppm
<150 ppm
<150 ppm
<100 ppm
<100 ppm
<150 ppm
<150 ppm
<150 ppm
<100 ppm
<100 ppm
<150 ppm
<150 ppm
<150 ppm
<100 ppm
<100 ppm