B Testing Batteries; Shallow Discharge Test - Huawei UPS2000-A-6KTTL User Manual

Table of Contents

Advertisement

UPS2000-A-(6 kVA-10 kVA)
User Manual (App)
B.1 Shallow Discharge Test
Before performing a battery shallow discharge test, ensure that:
● No high temperature, charger fault, or discharger fault has occurred.
● The load fluctuation is less than 10%.
Automatic Shallow Discharge Test
Step 1 On the app, choose Config > Battery Parameters, and set Shallow discharge
test to Enable.
Step 2 Set the Scheduled shallow discharge test interval(Day) as required. After
setting is complete, the system will perform automatic shallow discharge tests
based on the settings.
----End
Manual Shallow Discharge Test
Step 1 Adjust the discharge ratio for the shallow discharge test.
On the app, choose Configuration > Battery Parameters > Discharge ratio(%)
to check and adjust the discharge ratio as required.