Connecting Unshielded Cables
Unshielded cables are used to connect the I/O devices and the supply voltage to the Inline
Controller.
Connect these cables to the relevant Inline connectors using the spring-cage connection
method. You may connect cables with diameters of 0.2 mm
Figure A-1
Connecting unshielded cables
Wire the connectors as required for your application.
When wiring, proceed as follows:
•
Strip 8 mm off the cable.
Inline wiring is normally done without ferrules. However, it is possible to use ferrules. If
using ferrules, make sure they are properly crimped.
•
Push a screwdriver into the slot for the appropriate connection (Figure A-1, detail 1),
so that you can plug the wire into the spring opening.
Phoenix Contact recommends the SFZ 1-0,6x3,5 screwdriver (Order No. 1204517).
•
Insert the wire (Figure A-1, detail 2). Remove the screwdriver from the opening. This
clamps the wire.
After installation, the wires and the terminal points should be labeled.
2
2
to 1.5 mm
.