Technical Data And Ordering Data; Technical Data - Phoenix Contact ILC 330 User Manual

Inline controllers
Table of Contents

Advertisement

5

Technical Data and Ordering Data

General Data
Dimensions
Weight
Connection data of Inline-connector
Connection method
Conductor cross-section
General Supply
Use a power supply without fall-back characteristic curve (see Section "Sizing of the Power Supply" on page 2-24).
24 V Main Supply U
M
Connection method
Nominal value
Tolerance
Ripple
Current consumption at nominal voltage (typical)
Current consumption at nominal voltage (maximum)
Continuation
Safety equipment
Surge voltage
Polarity reversal
Provide an external fuse for the 24 V area. The power supply unit must be able to supply 4 times (400%) the nominal current of the external
fuse, to ensure that the fuse blows safely in the event of an error.
6959_en_05
5.1

Technical Data

Technical Data and Ordering Data
182 mm x 141.1 mm x 71.5 mm (75 mm with switch)
500 g, approximately
Spring-cage terminals
2
2
0.2 mm
to 1.5 mm
(solid or stranded), AWG 26-14
Spring-cage terminals
24 V DC
-20% / +20%
±5%
6 mA + 7 mA for each input set
8 A
Through potential routing
Input protective diodes (can be destroyed by permanent overload)
Pulse loads up to 1500 W are short circuited by the input protective diode.
Parallel diodes against polarity reversal; in the event of an error the high
current through the diodes causes the preconnected fuse to blow.
5-1