UM EN ILC 330/350
Figure 2-21
Overload range with fall-back
characteristic curve
2-24
PHOENIX CONTACT
2.14
Power Supply
2.14.1
Sizing of the Power Supply
Use a power supply unit suitable for the currents in your application. The selection depends
on the bus configuration, the resulting maximum currents and the type of supply (separate
supply of U
, U
and U
ILC
M
A power supply without a fall-back characteristic curve must be used for correct
operation of the Inline Controller (see Figure 2-22).
When the Inline Controller is switched on, an increased inrush current is temporarily
triggered. The Inline Controller behaves like a capacitive load when it is switched on.
Some electronically controlled power supplies have a fall-back characteristic curve (see
Figure 2-21). They are not suitable for operation with capacitive loads.
A primary switched-mode power supply unit (without fall-back characteristic curve) from
the QUINT POWER range (see INTERFACE catalog from Phoenix Contact) is
recommended for Inline Controller operation.
, or supply from one power supply unit).
S
Figure 2-22
Overload range without fall-back
characteristic curve
6959_en_05