Mounting And Removing The Inline Controller - Phoenix Contact ILC 330 User Manual

Inline controllers
Table of Contents

Advertisement

UM EN ILC 330/350
Mounting location
DIN rail
End clamp
End plate
Mounting position
2-16
PHOENIX CONTACT
2.11

Mounting and Removing the Inline Controller

For notes and instructions on mounting and removing Inline terminals, please refer to the
IB IL SYS PRO UM E user manual (for INTERBUS), the IL SYS INST UM E Inline
installation manual or the Inline system manual for your bus system.
Before mounting or removing the Inline Controller, ensure that the power supply is
switched off and cannot be switched on again by unauthorized persons.
An Inline station is set up by mounting the individual components side by side. No tools are
required. Mounting the components side by side automatically creates potential and bus
signal connections between the individual station components.
The modules are mounted perpendicular to the DIN rail.
As all other terminals of the Inline product range the Inline Controller has IP20 protection
and is designed for use in a closed control cabinet or control box (terminal box) with IP54
protection or higher.
The Inline Controller is mounted on a 35 mm standard DIN rail.
Fix the DIN rail on which the Inline Controller is mounted several times, especially in the
area around the Inline Controller. This makes it easier to remove the Inline Controller.
Mount end clamps on both sides of the Inline station. The end clamps ensure that the Inline
station is correctly mounted. End clamps fix the Inline station on both sides and keep it from
moving from side to side on the DIN rail. Phoenix Contact recommends using
CLIPFIX 35-5 end clamps (Order No. 3022276).
The mechanical end of an Inline station is the end plate. It has no electrical function. It
protects the station against ESD pulses and the user against dangerous contact voltage.
The end plate is supplied together with the Inline Controller and does not need to be
ordered separately.
When mounting or removing, the Inline Controller must be tilted. This means that no
Inline terminal must be installed directly to the right of the Inline Controller during
mounting and removing. The terminal must be removed prior to mounting or removing
the Inline Controller. Otherwise, the locking clips and jumper contacts are damaged.
Mount the Inline Controller horizontally (as shown in Figure 2-13). The specified
temperature range (see "Ambient Conditions" on page 5-6) is only guaranteed if the Inline
Controller is mounted in this position.
6959_en_05