2.7 Operating modes

3 operating
The instrument has 3 operating modes:
modes
- normal operation
- timed operation
- event operation
The following settings can, among others, be made for each of the three oper-
ating modes:
- stored value
- storage rate
Stored value
The stored value determines whether the average, minimum, maximum or in-
stantaneous value of the time interval between two storage cycles or the peak
values (envelope) are stored. When "peak value" is set, then the minimum and
maximum values of the last storage cycle are stored.
Storage rate
The storage rate determines the time interval between two stored values. The
diagram speed corresponds to the storage rate, which means that at a storage
rate of 5sec, for example, the stored value is entered in the diagram every 5
sec.
Normal
Normal operation is active whenever event or timed operation is not active.
operation
Timed
For timed operation, a period of time can be determined (24 hrs max.) within
operation
which a specific stored value and a specific storage rate are active.
Event operation
Event operation is active as long as its operating signal (v Chapter 4.2.6
"Configuration - Measurement storage") is active. Event operation can be
used, for example, to shorten the storage rate when an alarm is present.
Priority
The respective priorities of the operating modes are allocated as follows:
Operating mode
Normal operation
Timed operation
Event operation
Active
The active operating mode is indicated in the diagram by the background col-
operating
or for the diagram speed:
mode
Operating mode
Normal operation
Timed operation
Event operation
v Chapter 2.2 "Operating principle and graphic elements"
All manuals and user guides at all-guides.com
Priority
low
average
high
Color
gray
turquoise
orange
2 Instrument description