(7) Perform all risk assessments and safety level certification to the machine or the system as a whole.
It is recommended that a Certification Body final safety certification of the system be used.
(8) To prevent accumulation of multiple malfunctions, perform a malfunction check at regular intervals as
deemed necessary by the applicable safety standard. Regardless of the system safety level, malfunction
checks should be performed at least once per year.
(9) If the upper and lower power module in the servo amplifier are shorted and damaged simultaneously, the
servo motor may make a half revolution at a maximum. For a linear servo motor, the primary side will
move a distance of pole pitch.
App. 7.5 Block diagram and timing chart
(1) Function block diagram
+24V
DCDC
DCDC
power
0V
SW1 SW2
(2) Operation sequence
Power supply
A
1
2
A-axis shutdown 1 and 2 Energizing (close)
SDI
B
1
2
B-axis shutdown 1 and 2 Shut-off (open)
A
A-axis EMG start/reset Release (close)
SRES
B
B-axis EMG start/reset Normal (open)
A STO1
2
A-axis STO state 1 and 2 Normal (close)
STO
B STO1
2
B-axis STO state 1 and 2 Shut-off (open)
Note. Refer to App. 7.10.
SRESA+ SRESA-
TOF1A
TOF2A
Safety logic
TIMER1
TIMER2
SDI1A-
SDI2A-
SDI1B-
SDI2B-
15ms
15 ms or longer
( )
( )
50ms
50 ms or longer
( )
( )
( )
( )
STO
STO status
App. - 12
TOFA
STO1A+ STO2A+
STO1A-
STO2A-
10ms
10 ms or shorter
Control enabled
A
A-axis circuit
SDO1A+ SDO2A+
B
B-axis circuit
SDO1A- SDO2A-
(SW1
SW2)( )
Shut off delay (SW1 and SW2) (Note)
STO
STO status
Control enabled