Electrical Characteristics (Input Rectifier); Electrical Characteristics (Intermediate Dc Circuit) - PROLiNK Master III Series User Manual

Tower type
Table of Contents

Advertisement

8-4 Electrical Characteristics (Input Rectifier)

Table 8-4: Rectifier AC input (mains)
Rated power (KVA)
Rated AC input voltage
Input voltage tolerance
Frequency
Power factor
Harmonic current distortion
Max. current / phase
Icc

8-5 Electrical Characteristics (Intermediate DC Circuit)

Table 8-5: Battery
Intermediate DC circuit
Battery
Number of lead-acid
cells
Float voltage
Temperature
Compensation
(option)
Ripple voltage
Ripple current
Boost voltage
EOD voltage
Battery charge
Battery charging
power
1
max current
Note:
1. At low input voltage the UPS recharging capability increases and load decreases (up to the maximum
capacity indicated).
Unit
Vac
Vac
Hz
kW/kVA
THDI%
A
kA
Nominal
Maximum
Minimum
V/cell
2.28V/cell
mV/℃/cl
0~-5
% V float
≤1
% C10
≤5
VRLA
2.35V/cell
V/cell
1.67-1.83V/cell (adjustable)
V/cell
Constant current and constant voltage charge mode
24A(adjustable) @ 100KVA Model
A
36A(adjustable) @ 120KVA Model
54A(adjustable) @ 180KVA/200KVA Model
100~200KVA
380/400/415 (3-phase and sharing neutral with the
bypass input)
305 ~ 478; 208 ~ 304(output derated below 70%)
50/60 (tolerance: 40Hz ~ 70Hz)
0.99 (0.97) full load(half load)
<4 (full load)
100KVA/100KW
120KVA/120KW
180KVA/180KW
200KVA/200KW
≤ 10kA
External battery
216 (6cells x 36 12V battery block)
240 (6cells x 40 12V battery block)
192 (6cells x 32 12V battery block)
70
183
220
330
366