2-10 Power Cable

Please follow the local wiring regulations. Follow environmental conditions and refer to
IEC60950-1.
2-10.1
AC input and output current and power cable configuration.
Power rating
Current (A)
Power cable (mm
2
)
Fixation torque force (lb-in)

2-11 Wiring

WARNING:
l
Before connecting any wire, make sure the AC input and battery power is completely cut off.
l
Make sure the breakers, Main Breaker, Bypass Breaker, Maintenance Breaker, Output Breaker and
battery breaker are all in the OFF position.
l
Make sure the Maintenance Bypass Switch is in UPS position.
l
In order to have good heat dissipation, the power cables MUST come into the cabinet from of the cabinet.
Or the cables will block the cooling ventilation and make the over temperature failure.
100KVA
120KVA
277
332
150
185
60
60
18
180KVA
200KVA
498
554
120 x 2
150 x 2
60
60

Advertisement