Lenovo ThinkSystem SD650 V3 User Manual page 183

Neptune dwc tray
Hide thumbs Also See for ThinkSystem SD650 V3:
Table of Contents

Advertisement

Figure 182. Water loop installation
Step 8.
Ensure the processors are secured properly.
a.
Rotate the anti-tilt wire bails (8x anti-tilt wire bails per node) outwards to the locked position.
b.
Fully tighten all Torx T30 captive screws (8x Torx T30 captive screws per node) on cold
plates in the installation sequence shown on the cold plate label (with a torque screwdriver set
to the proper torque).
Note: For reference, the torque required for the screws to be fully tightened/removed is 0.9-1.3
newton-meters, 8-12 inch-pounds.
Attention: To prevent damage to components, make sure that you follow the indicated tightening
sequence.
.
Chapter 5
Hardware replacement procedures
175