Switch-Off Delay; Failure Mode; Switch Status; Invert Output Signal - Endress+Hauser Levelflex FMP55 Operating Instructions Manual

Profibus pa guided wave radar
Hide thumbs Also See for Levelflex FMP55:
Table of Contents

Advertisement

Levelflex FMP55 PROFIBUS PA

Switch-off delay

Navigation
Prerequisite
Description
User entry

Failure mode

Navigation
Prerequisite
Description
Selection
Additional information

Switch status

Navigation
Description

Invert output signal

Navigation
Description
Selection
Endress+Hauser
 Setup → Advanced setup → Switch output → Switch-off delay
• Switch output function (→  141) = Limit
• Assign limit (→  142) ≠ Off
Define delay for the switch-off of status output.
0.0 to 100.0 s
 Setup → Advanced setup → Switch output → Failure mode
Switch output function (→  141) = Limit or Digital Output
Define output behavior in alarm condition.
• Actual status
• Open
• Closed
 Setup → Advanced setup → Switch output → Switch status
Shows the current switch output status.
 Setup → Advanced setup → Switch output → Invert outp.sig.
Invert the output signal.
• No
• Yes
Operating menu