Commissioning (block-oriented operation)
96
incompatible. These should be categorized as Function check (C) and no longer as
Failure (F).
1.
In the FieldCare navigation window, navigate to Expert → Communication → Field
diagnostics → Alarm detection enable.
2.
 32
The "Fail Map" and "Check Map" columns in the as-delivered state
In the Fail Map column, look for the Configuration Highest Severity group and
uncheck the corresponding check box (A). Check the relevant check box in the Check
Map (B) column. Note that you must press the Enter key to confirm every entry.
Levelflex FMP56, FMP57 FOUNDATION Fieldbus