Levelflex FMP56, FMP57 PROFIBUS PA Important document information Important document information Document function These Operating Instructions contain all the information that is required in various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal.
Important document information Levelflex FMP56, FMP57 PROFIBUS PA 1.2.3 Tool symbols Symbol Meaning Torx screwdriver A0013442 Flat blade screwdriver A0011220 Cross-head screwdriver A0011219 Allen key A0011221 Hexagon wrench A0011222 1.2.4 Symbols for certain types of information Symbol Meaning Permitted Procedures, processes or actions that are permitted.
Levelflex FMP56, FMP57 PROFIBUS PA Important document information Symbol Meaning Hazardous area Indicates a hazardous area. Safe area (non-hazardous area) Indicates the non-hazardous area. 1.2.6 Symbols at the device Symbol Meaning Safety instructions Observe the safety instructions contained in the associated Operating Instructions.
For an overview of the scope of the associated Technical Documentation, refer to the following: • The W@M Device Viewer : Enter the serial number from the nameplate (www.endress.com/deviceviewer) • The Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the 2-D matrix code (QR code) on the nameplate. Endress+Hauser...
Levelflex FMP56, FMP57 PROFIBUS PA Important document information 1.3.1 Safety Instructions (XA) Depending on the approval, the following Safety Instructions (XA) are supplied with the device. They are an integral part of the Operating Instructions. Feature 010 Approval Available for Feature 020: "Power Supply;...
Page 10
Important document information Levelflex FMP56, FMP57 PROFIBUS PA Feature 010 Approval Available for Feature 020: "Power Supply; Output" IEC Ex d [ia] IIC T6 Ga/Gb, Ex t IIIC Da/Db • FMP56 XA00503F XA00503F XA00503F XA00523F XA01136F • FMP57 KC Ex ia IIC T6 Ga •...
Page 11
Levelflex FMP56, FMP57 PROFIBUS PA Important document information Ex-marking in case of connected FHX50 remote display If the device is prepared for the remote display FHX50 (product structure: feature 030: Display, Operation", option L or M), the Ex marking of some certificates changes according to the following table Feature 010 ("Approval") Feature 030 ("Display, Operation") Ex-marking...
The manufacturer is not liable for damage caused by improper or non-designated use. Verification for borderline cases: ‣ For special measured materials and cleaning agents, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of wetted materials, but does not accept any warranty or liability.
The measuring system meets the legal requirements of the applicable EC guidelines. These are listed in the corresponding EC Declaration of Conformity together with the standards applied. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark. 2.5.2 EAC conformity The measuring system meets the legal requirements of the applicable EAC guidelines.
Product description Levelflex FMP56, FMP57 PROFIBUS PA Registered trademarks PROFIBUS ® Registered trademark of the PROFIBUS User Organization, Karlsruhe, Germany KALREZ ® , VITON ® Registered trademark of DuPont Performance Elastomers L.L.C., Wilmington, USA TEFLON ® Registered trademark of E.I. DuPont de Nemours & Co., Wilmington, USA TRI CLAMP ®...
• Enter the serial number from the nameplates into the Endress+Hauser Operations App or scan the 2-D matrix code (QR code) on the nameplate with the Endress+Hauser Operations App: all the information for the measuring device is displayed. Endress+Hauser...
Levelflex FMP56, FMP57 PROFIBUS PA Storage, Transport Storage, Transport Storage conditions • Permitted storage temperature: –40 to +80 °C (–40 to +176 °F) • Use the original packaging. Transport product to the measuring point WARNING Housing or probe may be damaged or break away.
Mounting Levelflex FMP56, FMP57 PROFIBUS PA Mounting Mounting requirements 6.1.1 Suitable mounting position A0021468 4 Mounting requirements for Levelflex Mounting distances • Distance (A) between wall and rod or rope probe: – for smooth metallic walls: > 50 mm (2 in) –...
Page 21
Levelflex FMP56, FMP57 PROFIBUS PA Mounting Additional conditions • When mounting in the open, a weather protection cover (1) may be installed to protect the device against extreme weather conditions. • In metallic vessels: Preferably do not mount the probe in the center of the vessel (2), as this would lead to increased interference echoes.
Mounting Levelflex FMP56, FMP57 PROFIBUS PA 6.1.2 Applications with restricted mounting space Mounting with remote sensor The device version with a remote sensor is suited for applications with restricted mounting space. In this case the electronics housing is mounted at a separate position from which it is easier accessible.
Levelflex FMP56, FMP57 PROFIBUS PA Mounting 6.1.3 Notes on the mechanical load of the probe Tensile load limit of rope probes Sensor Feature 060 Probe Tensile load limit [kN] Max. rupture load [kN] FMP56 LA, LB Rope 4mm (1/6") 316 NB, NE Rope 6mm (1/4") PA>Steel...
Page 24
Mounting Levelflex FMP56, FMP57 PROFIBUS PA L [m] A0017170 5 Silica sand in silo with smooth metallic walls; tensile load as a function of level L for rope diameters 6mm (0,24 in) and 4mm (0,16 in) Silo diameter 12 m (40 ft)
Page 25
Levelflex FMP56, FMP57 PROFIBUS PA Mounting L [m] A0017172 7 Wheat in silo with smooth metallic walls; tensile load as a function of level L for rope diameters 6mm (0,24 in) and 4mm (0,16 in) Silo diameter 12 m (40 ft)
Page 26
Mounting Levelflex FMP56, FMP57 PROFIBUS PA Bending strength of rod probes Sensor Feature 060 Probe Bending strength [Nm] FMP57 AE, AF Rod 16mm (0.63") 316L Endress+Hauser...
Levelflex FMP56, FMP57 PROFIBUS PA Mounting 6.1.4 Notes on the process connection Probes are mounted to the process connection with threaded connections or flanges. If during this installation there is the danger that the probe end moves so much that it touches the tank floor or cone at times, the probe must, if necessary, be shortened and fixed down →...
Page 28
Mounting Levelflex FMP56, FMP57 PROFIBUS PA Nozzle mounting ø 150 (6) £ A0015122 Length H of the rigid part of the rope probe Probe FMP56, rope 4 mm (0.16 in) 94 mm (3.7 in) FMP57, rope 4 mm (0.16 in) 120 mm (4.7 in)
Page 29
Levelflex FMP56, FMP57 PROFIBUS PA Mounting Rod extension/centering HMP40 for FMP57 For FMP57 with rope probes the rod extension/centering HMP 40 is available as an accessory → 96. It has to be used if otherwise the probe rope comes into contact with the lower edge of the nozzle.
Page 30
Mounting Levelflex FMP56, FMP57 PROFIBUS PA Installation in nozzles ≥ DN300 If installation in ≥ 300mm/12" nozzles is unavoidable, installation must be carried out in accordance with the following sketch. A0014199 Lower edge of the nozzle Approx. flush with the lower edge of the nozzle (± 50 mm/2") Plate Pipe ...
Levelflex FMP56, FMP57 PROFIBUS PA Mounting 6.1.5 Securing the probe Securing rope probes A0012609 Sag of the rope: ≥ 1 cm per 1m of the probe length (0.12 inch per 1 ft of the probe length) Reliably grounded end of probe...
Page 32
Mounting Levelflex FMP56, FMP57 PROFIBUS PA Securing rod probes • For WHG approvals: For probe lengths ≥ 3 m (10 ft) a support is required. • In general, rod probes must be supported if there is a horizontal flow (e.g. from an agitator) or in the case of strong vibrations.
Extension rod / Centering HMP40 (see "Accessories") Note for installations with rod extension/center washer (accessories): Strong dust generation can lead to build-up behind the center washer. This can cause an interference signal. For other installation possibilities please contact Endress+Hauser. Endress+Hauser...
Page 34
Mounting Levelflex FMP56, FMP57 PROFIBUS PA Installation from the side mm (in) A0014140 • If installation from above is not possible, the Levelflex can also be mounted from the side. • In this case, always fix the rope probe → 31 .
Page 35
Levelflex FMP56, FMP57 PROFIBUS PA Mounting Non-metallic vessels A0012527 Non-metallic vessel Metal sheet or metal flange To ensure reliable measurements in non-metallic vessels: • Select an instrument version with metal flange (minimum size DN50/2"). • Or: mount a metal sheet with a diameter of at least 200 mm (8 in) to the probe at the process connection.
Page 36
Mounting Levelflex FMP56, FMP57 PROFIBUS PA Vessels with heat insulation If process temperatures are high, the device must be included in normal tank insulation to prevent the electronics heating up as a result of heat radiation or convection. The insulation may not exceed beyond the points labeled "MAX" in the drawings.
Levelflex FMP56, FMP57 PROFIBUS PA Mounting Mounting the device 6.2.1 Required mounting tools • For mounting thread 3/4": Hexagonal wrench 36 mm • For mounting thread 1-1/2": Hexagonal wrench 55 mm • To shorten rod or coax probes: Saw • To shorten rope probes: –...
Page 38
Mounting Levelflex FMP56, FMP57 PROFIBUS PA A0021693 Rope material Torque for set screws 4 mm (0.16 in) 40 mm (1.6 in) 3 mm 5 Nm (3.69 lbf ft) 6 mm (0.24 in) 55 mm (2.2 in) 4 mm 15 Nm (11.06 lbf ft) PA >...
Levelflex FMP56, FMP57 PROFIBUS PA Mounting 6.2.3 Mounting the device Mounting devices with thread A0012528 Devices with mounting thread are screwed into a welding boss or a flange and are usually also secured with these. • Tighten with the hexagonal nut only: –...
Mounting Levelflex FMP56, FMP57 PROFIBUS PA A0012529 When lowering the rope probe into the vessel, observe the following: • Uncoil rope and lower it slowly and carefully into the vessel. • Do not kink the rope. • Avoid any backlash, since this might damage the probe or the vessel fittings.
Page 41
Levelflex FMP56, FMP57 PROFIBUS PA Mounting Mounting the electronics housing ø42...60 (1.65...2.36) 122 (4.8) 140 (5.5) 175 (6.9) 158 (6.2) A0014793 12 Mounting the electronics housing using the mounting bracket; dimensions: mm (in) Wall mounting Pipe mounting Connecting the cable...
Mounting Levelflex FMP56, FMP57 PROFIBUS PA 6.2.5 Turning the transmitter housing To provide easier access to the connection compartment or display module, the transmitter housing can be turned: max. 350° 8 mm 8 mm A0013713 1. Unscrew the securing screw using an open-ended wrench.
Levelflex FMP56, FMP57 PROFIBUS PA Mounting Post-installation check Is the device undamaged (visual inspection)? Does the device conform to the measuring point specifications? For example: • Process temperature • Process pressure (refer to the chapter on "Material load curves" of the "Technical Information"...
Levelflex FMP56, FMP57 PROFIBUS PA Electrical connection Connection examples for the switch output A0015909 15 Connection of a relay A0015910 16 Connection of a digital input Suitable relays (examples): Pull-up resistor • Solid-state relay: Phoenix Contact OV-24DC/480AC/5 with mounting...
Electrical connection Levelflex FMP56, FMP57 PROFIBUS PA 7.1.3 Device plug connectors For the versions with fieldbus plug connector (M12 or 7/8"), the signal line can be connected without opening the housing. Pin assignment of the M12 plug connector Meaning Signal +...
< 1.5 pF Nominal arrest impulse voltage (8/20 μs) 10 kA External overvoltage protection HAW562 or HAW569 from Endress+Hauser are suited as external overvoltage protection. For detailed information please refer to the following documents: • HAW562: TI01012K • HAW569: TI01013K...
Electrical connection Levelflex FMP56, FMP57 PROFIBUS PA Connecting the device WARNING Explosion hazard! ‣ Comply with the relevant national standards. ‣ Observe the specifications in the Safety Instructions (XA). ‣ Only use the specified cable glands. ‣ Check whether the supply voltage matches the specifications on the nameplate.
Levelflex FMP56, FMP57 PROFIBUS PA Electrical connection A0013837 Connect the cable in accordance with the terminal assignment → 44. 8. When using screened cable: Connect the cable screen to the ground terminal. 9. Screw the cover onto the connection compartment.
Page 50
Electrical connection Levelflex FMP56, FMP57 PROFIBUS PA If required: Is the protective earth connected correctly ? If supply voltage is present: Is the device ready for operation and do values appear on the display module? Are all housing covers installed and firmly tightened?
Levelflex FMP56, FMP57 PROFIBUS PA Operation options Operation options Overview 8.1.1 Local operation Operation Pushbuttons Touch Control with Order code for Option C "SD02" Option E "SD "Display; Operation" A0032219 A0032221 Display 4-line display 4-line display elements white background lighting; switches to red in...
Operation options Levelflex FMP56, FMP57 PROFIBUS PA 8.1.2 Operation with remote display and operating module FHX50 A0013137 17 FHX50 operating options Housing of the remote display and operating module FHX50 Display and operating module SD02, push buttons; cover must be removed Display and operating module SD03, optical keys;...
Page 53
Levelflex FMP56, FMP57 PROFIBUS PA Operation options Via service interface (CDI) A0014019 Service interface (CDI) of the measuring device (= Endress+Hauser Common Data Interface) Commubox FXA291 Computer with "FieldCare" operating tool Endress+Hauser...
Operation options Levelflex FMP56, FMP57 PROFIBUS PA Structure and function of the operating menu 8.2.1 Structure of the operating menu Menu Submenu / Meaning parameter Language Defines the operating language of the on-site display. Commissioning Opens the interactive wizard for a guided commissioning of the device.
Page 55
Levelflex FMP56, FMP57 PROFIBUS PA Operation options Menu Submenu / Meaning parameter Communication Contains all parameters needed to configure the digital communication interface. Diagnostics Contains all parameters needed to detect and analyze operational errors. In case of operation via operating tools (e.g. FieldCare), the "Language" parameter is located at "Setup → ...
Operation options Levelflex FMP56, FMP57 PROFIBUS PA 8.2.2 User roles and related access authorization The two user roles Operator and Maintenance have different write access to the parameters if a device-specific access code has been defined. This protects the device configuration via the local display from unauthorized access →...
Levelflex FMP56, FMP57 PROFIBUS PA Operation options 8.2.3 Write protection via access code Using the device-specific access code, the parameters for the measuring device configuration are write-protected and their values can no longer be changed via local operation. Define access code via local display 1.
Operation options Levelflex FMP56, FMP57 PROFIBUS PA 8.2.4 Disabling write protection via access code If the -symbol appears on the local display in front of a parameter, the parameter is write-protected by a device-specific access code and its value cannot be changed at the moment using the local display →...
Levelflex FMP56, FMP57 PROFIBUS PA Operation options 8.2.6 Write protection via write protection switch Unlike parameter write protection via a user-specific access code, this allows write access to the entire operating menu - except for the "Contrast display" parameter - to be locked.
Page 60
Operation options Levelflex FMP56, FMP57 PROFIBUS PA 4. Installing the lock switch (WP) on the main electronics module in the ON position enables the hardware write protection. Installing the lock switch (WP) on the main electronics module in the OFF position (factory setting) disables the hardware write protection.
Levelflex FMP56, FMP57 PROFIBUS PA Operation options 8.2.7 Enabling and disabling the keypad lock The keypad lock allows to disable access to the entire operating menu via local operation. Thus navigating through the operating menu or modifying the values of individual parameters is no longer possible.
Operation options Levelflex FMP56, FMP57 PROFIBUS PA Display and operating module 8.3.1 Display appearance User ABC_ DEFG HIJK PQRS TUVW LMNO A0012635 18 Appearance of the display and operation module for on-site operation Measured value display (1 value max. size) 1.1 Header containing tag and error symbol (if an error is active)
Page 63
Levelflex FMP56, FMP57 PROFIBUS PA Operation options Display symbols for the submenus Symbol Meaning Display/operation Is displayed: • in the main menu next to the selection "Display/operation" A0011975 • in the header, if you are in the "Display/operation" menu Setup Is displayed: •...
Page 64
Operation options Levelflex FMP56, FMP57 PROFIBUS PA Measured value symbols Symbol Meaning Measured values Level A0011995 Distance A0011996 Current output A0011998 Measured current A0011999 Terminal voltage A0012106 Temperature of the electronics or the sensor A0012104 Measuring channels Measuring channel 1...
Levelflex FMP56, FMP57 PROFIBUS PA Operation options 8.3.2 Operating elements Meaning Minus key For menu, submenu Moves the selection bar upwards in a picklist. A0013969 For text and numeric editor In the input mask, moves the selection bar to the left (backwards).
Operation options Levelflex FMP56, FMP57 PROFIBUS PA 8.3.3 Entering numbers and text Numeric editor Text editor User ABC_ DEFG HIJK LMNO PQRS TUVW A0013999 A0013941 Editing view Display area of the entered values Input mask Operating elements Input mask The following input symbols are available in the input mask of the numeric and text editor:...
Page 67
Levelflex FMP56, FMP57 PROFIBUS PA Operation options Confirms selection. A0013985 Switches to the selection of the correction tools. A0013987 Exits the input without applying the changes. A0013986 Clears all entered characters. A0014040 Correction symbols under Clears all entered characters. A0013989 Moves the input position one position to the right.
Operation options Levelflex FMP56, FMP57 PROFIBUS PA 8.3.4 Opening the context menu Using the context menu, the user can call up the following menus quickly and directly from the operational display: • Setup • Conf. backup disp. • Simulation Calling up and closing the context menu The user is in the operational display.
Levelflex FMP56, FMP57 PROFIBUS PA Operation options 8.3.5 Envelope curve on the display and operating module In order to assess the measuring signal, the envelope curve and - if a mapping has been recorded - the mapping curve can be displayed:...
Integration into a PROFIBUS network Levelflex FMP56, FMP57 PROFIBUS PA Integration into a PROFIBUS network Overview of the device database files (GSD) Manufacturer ID 17 (0x11) Ident number 0x1558 Profile version 3.02 GSD file Information and files under: • www.endress.com GSD file version •...
Page 71
Levelflex FMP56, FMP57 PROFIBUS PA Integration into a PROFIBUS network A0015903 21 Example of software addressing; switch 8 is in position "ON"; the address is defined in the operating menu (Setup → Device address) Endress+Hauser...
Commissioning via wizard Levelflex FMP56, FMP57 PROFIBUS PA Commissioning via wizard A wizard guiding the user through the initial setup is available in FieldCare and DeviceCare. 1. Connect the device to FieldCare or DeviceCare → 52. 2. Open the device in FieldCare or DeviceCare.
Levelflex FMP56, FMP57 PROFIBUS PA Commissioning via operating menu Commissioning via operating menu 11.1 Installation and function check Make sure that all final checks have been completed before you start up your measuring point: • Checklist "Post-installation check" → 43 •...
Commissioning via operating menu Levelflex FMP56, FMP57 PROFIBUS PA 11.3 Configuration of a level measurement 20 mA 100% 4 mA A0012838 23 Configuration parameters for level measurements in solids Length of probe Reference point of the measurement Distance Level...
Page 75
Levelflex FMP56, FMP57 PROFIBUS PA Commissioning via operating menu 10. For operation via local display: Navigate to: Setup → Mapping → Confirm distance Compare the displayed distance to the real distance in order to start the recording of the mapping curve if required.
Commissioning via operating menu Levelflex FMP56, FMP57 PROFIBUS PA 11.4 Recording the reference curve After the configuration of the measurement it is recommended to record the current envelope curve as a reference curve. The reference curve can be used later on in the process for diagnostic purposes.
Levelflex FMP56, FMP57 PROFIBUS PA Commissioning via operating menu 11.5 Configuration of the on-site display 11.5.1 Factory settings of the on-site display for level measurements Parameter Factory setting for devices with 1 current Factory setting for devices with 2 current...
Commissioning via operating menu Levelflex FMP56, FMP57 PROFIBUS PA 11.6 Configuration management After commissioning, you can save the current device configuration, copy it to another measuring point or restore the previous device configuration. You can do so using the Configuration management parameter and its options.
Levelflex FMP56, FMP57 PROFIBUS PA Commissioning via operating menu 11.7 Protection of the settings against unauthorized changes There are two ways to protect the settings against unauthorized changes: • Via parameter settings (software locking) → 57 • Via locking switch (hardware locking) → 59...
Diagnostics and troubleshooting Levelflex FMP56, FMP57 PROFIBUS PA Diagnostics and troubleshooting 12.1 General trouble shooting 12.1.1 General errors Error Possible cause Remedial action Device does not respond. Supply voltage not connected. Connect the correct voltage. The cables do not contact the Ensure electrical contact between the terminals properly.
Levelflex FMP56, FMP57 PROFIBUS PA Diagnostics and troubleshooting 12.1.2 Parametrization errors Parametrization errors for level measurements Error Possible cause Remedial action Measured value wrong If measured distance(Setup • Check and adjust the Empty → Distance) matches the real calibration parameter (→ 115) if distance: necessary.
Diagnostics and troubleshooting Levelflex FMP56, FMP57 PROFIBUS PA 12.2 Diagnostic information on local display 12.2.1 Diagnostic message Faults detected by the self-monitoring system of the measuring device are displayed as a diagnostic message in alternation with the measured value display.
Page 83
Levelflex FMP56, FMP57 PROFIBUS PA Diagnostics and troubleshooting Diagnostics event and event text The fault can be identified using the diagnostics event. The event text helps you by providing information about the fault. In addition, the corresponding symbol is displayed before the diagnostics event.
Diagnostics and troubleshooting Levelflex FMP56, FMP57 PROFIBUS PA 12.2.2 Calling up remedial measures X X X X X X X X X X X X X X 20.50 S801 Supply voltage Menu Diagnostic list Diagnostics 1 S801 Supply voltage Diagnostics 2...
Levelflex FMP56, FMP57 PROFIBUS PA Diagnostics and troubleshooting 12.3 Diagnostic event in the operating tool If a diagnostic event is present in the device, the status signal appears in the top left status in the operating tool along with the corresponding symbol for event level in accordance with NAMUR NE 107: •...
Diagnostics and troubleshooting Levelflex FMP56, FMP57 PROFIBUS PA 12.5 List of diagnostic events Diagnostic Short text Remedy instructions Status Diagnostic number signal behavior [from the [from the factory] factory] Diagnostic of sensor Broken probe detected 1. Check map Alarm 2. Check sensor...
Levelflex FMP56, FMP57 PROFIBUS PA Diagnostics and troubleshooting Diagnostic Short text Remedy instructions Status Diagnostic number signal behavior [from the [from the factory] factory] Linearization Check linearization table Alarm Configuration 1. Restart device Alarm incompatible 2. Contact service Dataset 1. Check data set file Warning 2.
Diagnostics and troubleshooting Levelflex FMP56, FMP57 PROFIBUS PA Navigation path Diagnostics → Event logbook → Event list A maximum of 100 event messages can be displayed in chronological order. The event history includes entries for: • Diagnostic events • Information events...
Page 89
Levelflex FMP56, FMP57 PROFIBUS PA Diagnostics and troubleshooting Info number Info name I1185 Display backup done I1186 Restore via display done I1187 Settings downloaded with display I1188 Display data cleared I1189 Backup compared I1256 Display: access status changed I1264 Safety sequence aborted...
Diagnostics and troubleshooting Levelflex FMP56, FMP57 PROFIBUS PA 12.7 Firmware history Date Software Modifications Documentation (FMP56, FMP57, PROFIBUS) version Operating Instructions Description of Parameters Technical Information 07.2011 01.00.zz Original software BA01009F/00/EN/10.10 GP01001F/00/EN/10.10 TI01004F/00/EN/13.11 02.2015 01.01.zz • Support of SD03 BA01009F/00/EN/14.14 GP01001F/00/EN/13.14...
Levelflex FMP56, FMP57 PROFIBUS PA Maintenance Maintenance The measuring device requires no special maintenance. 13.1 Exterior cleaning When exterior-cleaning the device, always use cleaning agents that do not attack the surface of the hosuing and the seals. Endress+Hauser...
14.1.1 Repair concept The Endress+Hauser repair concept assumes that the devices have a modular design and that repairs can be done by the Endress+Hauser service or specially trained customers. Spare parts are contained in suitable kits. They contain the related replacement instructions.
The measuring device must be returned if it is need of repair or a factory calibration, or if the wrong measuring device has been delivered or ordered. Legal specifications require Endress+Hauser, as an ISO-certified company, to follow certain procedures when handling products that are in contact with the medium.
Accessories Levelflex FMP56, FMP57 PROFIBUS PA 15.1.3 Extension rod / centering HMP40 Accessory Description Extension rod / centering HMP40 • can be used for: FMP57 • Admissible temperature at lower nozzle edge: – without center washer: no limitation – with center washer: -40 to 150 °C...
Levelflex FMP56, FMP57 PROFIBUS PA Accessories 15.1.4 Mounting kit, isolated Accessory Description Mounting kit, isolated can be used for • FMP50 • FMP51 • FMP54 • FMP56 • FMP57 A0013586 29 Scope of supply of the mounting kit: Insulating sleeve Eye-bolt For reliably insulated fixing of the probe.
Levelflex FMP56, FMP57 PROFIBUS PA 15.2 Communication-specific accessories Accessory Description Commubox FXA291 Connects Endress+Hauser field devices with CDI interface (= Endress+Hauser Common Data Interface) to the USB interface of a computer. Order code: 51516983 For details refer to Technical Information TI00405C 15.3...
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu Operating menu 16.1 Overview of the operating menu (display module) Navigation Operating menu Language → 155 Setup → 114 Device tag → 114 Device address → 114 Distance unit →...
Page 102
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA Fail safe type → 123 Fail safe value → 123 ‣ Advanced setup → 124 Locking status → 124 Access status display → 125 → 125 Enter access code ‣...
Page 103
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu ‣ Edit table Level → 139 Customer value → 140 Activate table → 140 ‣ Safety settings → 141 Output echo lost → 141 Value echo lost → 141 Ramp at echo lost →...
Page 104
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA Switch-off value → 152 Switch-off delay → 153 Failure mode → 153 Switch status → 153 Invert output signal → 153 ‣ → 155 Display Language → 155 Format display →...
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA 16.2 Overview of the operating menu (operating tool) Navigation Operating menu Setup → 114 Device tag → 114 Device address → 114 Distance unit → 114 → 115...
Page 109
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu Enter access code → 125 ‣ Level → 126 Medium type → 126 Medium property → 126 Process property → 127 Advanced process conditions → 128 Level unit →...
Page 110
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA Value echo lost → 141 Ramp at echo lost → 142 Blocking distance → 129 ‣ WHG confirmation → 144 ‣ Deactivate WHG → 145 → 145...
Page 111
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu Format display → 155 Value 1 to 4 display → 157 Decimal places 1 to 4 → 157 Display interval → 157 Display damping → 158 Header → 158 Header text →...
Page 112
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA Timestamp → 168 Operating time from restart → 168 Operating time → 161 ‣ Diagnostic list → 169 Diagnostics 1 to 5 → 169 → 169 Timestamp 1 to 5 ‣...
Page 113
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu Out status → 176 Out status HEX → 176 ‣ Data logging → 177 Assign channel 1 to 4 → 177 Logging interval → 178 Clear logging data →...
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA 16.3 "Setup" menu • : Marks the navigation path to the parameter via the display and operating module. • : Marks the navigation path to the parameter via an operating tool (e.g. FieldCare).
Page 115
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu Bin type Navigation Setup → Bin type Prerequisite Medium type (→ 126) = Solid Description Specify bin type. Selection • Concrete • Plastic wood • Metallic • Aluminium • Buffer silo (fast) •...
Page 116
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA Full calibration Navigation Setup → Full calibr. Description Specify the distance F between the minimum level (0%) and the maximum level (100%). User entry Depending on the probe Factory setting Depending on the probe...
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu Distance Navigation Setup → Distance Description Displays the measured distance D between the reference point (lower edge of the flange or threaded connection) and the level. Additional information A0013201 33 Distance for bulk solid measurements The unit is defined in the Distance unit parameter (→...
Page 118
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA Confirm distance Navigation Setup → Confirm distance Description Specify, whether the measured distance matches the real distance. Depending on the selection the device automatically sets the range of mapping. Selection • Manual map •...
Page 119
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu Present mapping Navigation Setup → Present mapping Description Indicates up to which distance a mapping has already been recorded. Mapping end point Navigation Setup → Map. end point Prerequisite Confirm distance (→ 118) = Manual map or Distance too small Description Specify new end of the mapping.
Page 120
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA Additional information Meaning of the options • No The map is not recorded. • Record map The map is recorded. After the recording is completed, the new measured distance and the new mapping range appear on the display. When operating via the local display, these values must be confirmed by pressing .
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu 16.3.1 "Mapping" wizard The Mapping wizard is only available when operating via the local display. When operating via an operating tool, all parameters concerning the mapping are located directly in the Setup menu (→ 114).
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA 16.3.2 "Analog input 1 to 6" submenu There is an Analog input submenu for each AI block of the device. The AI block is used to configure the measured value transmission to the bus.
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu User entry Positive floating-point number Factory setting Additional information This parameter defines the damping constant τ (in seconds) for the output of the Analog Input Block. Fail safe type Navigation Expert → Analog inputs → Analog input 1 to 6 → Fail safe type...
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA 16.3.3 "Advanced setup" submenu Navigation Setup → Advanced setup Locking status Navigation Setup → Advanced setup → Locking status Description Indicates the write protection with the highest priority that is currently active.
• If no key is pressed for 10 min, or the user switches from the navigation and editing mode back to the measured value display mode, the device automatically locks the write- protected parameters after another 60 s. Please contact your Endress+Hauser Sales Center if you lose your access code. Endress+Hauser...
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA "Level" submenu Navigation Setup → Advanced setup → Level Medium type Navigation Setup → Advanced setup → Level → Medium type Description Specify type of medium. User interface • Liquid •...
• the Endress+Hauser DC manual (CP01076F) • the Endress+Hauser "DC Values App" (available for Android and iOS) For EOP level evaluation = Fix DC, the exact dielectric constant has to be entered into the DC value parameter. Therefore, the Medium property parameter is not available in this case.
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA For "Operating mode" = "Level" and "Medium type" = "Solid" Process property Step response time / s Very fast > 100 m (333 ft) /h Fast > 10 m (33 ft) /h Standard < 10 m (33 ft) /h Medium <...
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu Level unit Navigation Setup → Advanced setup → Level → Level unit Description Select level unit. Selection SI units US units • % • ft • m • in • mm...
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA Structure of the submenu on the display module Navigation Setup → Advanced setup → Linearization ‣ Linearization Linearization type → 134 Unit after linearization → 135 Free text → 136 Maximum value →...
Page 133
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu Structure of the submenu in an operating tool (e.g. FieldCare) Navigation Setup → Advanced setup → Linearization ‣ Linearization Linearization type → 134 Unit after linearization → 135 Free text →...
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu Meaning of the options • None The level is transmitted in the level unit without linearization. • Linear The output value (volume/weight) is directly proportional to the level L. This is valid, for example, for vertical cylinders.
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA Selection SI units US units Imperial units • STon • lb impGal • t • UsGal • kg • ft³ • cm³ • dm³ • m³ • hl • l • % Custom-specific units...
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu Maximum value Navigation Setup → Advanced setup → Linearization → Maximum value Prerequisite Linearization type (→ 134) has one of the following values: • Linear • Pyramid bottom • Conical bottom •...
Page 138
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA Additional information A0013264 Intermediate height The unit is defined in the Distance unit parameter (→ 114). Table mode Navigation Setup → Advanced setup → Linearization → Table mode Prerequisite Linearization type (→ 134) = Table Description Select editing mode of the linearization table.
Page 139
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu Conditions the linearization table must meet: • The table may consist of up to 32 pairs of values "Level - Linearized Value". • The table must be monotonic (monotonically increasing or decreasing). • The first linearization point must refer to the minimum level.
Page 140
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA Factory setting Level (Semiautomatic) Navigation Setup → Advanced setup → Linearization → Level Prerequisite • Linearization type (→ 134) = Table • Table mode (→ 138) = Semiautomatic Description Displays measured level (value before linearization). This value is transmitted to the table.
Page 141
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu "Safety settings" submenu Navigation Setup → Advanced setup → Safety sett. Output echo lost Navigation Setup → Advanced setup → Safety sett. → Output echo lost Description Define the behavior of the output signal in case of a lost echo.
Page 142
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA Ramp at echo lost Navigation Setup → Advanced setup → Safety sett. → Ramp echo lost Prerequisite Output echo lost (→ 141) = Ramp at echo lost Description Define the slope of the ramp in the case of a lost echo.
Page 143
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu due to a level change during operation. Signals which are already in the blocking distance when the device is switched on, are ignored. This behavior is only valid if the following two conditions are met: •...
Page 144
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA "WHG confirmation" wizard The WHG confirmation wizard is only available for devices with WHG approval (Feature 590: "Additional Approval", option LC: "WHG overfill prevention" ) which are currently not in the WHG-locked state.
Page 146
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA "Probe settings" submenu The Probe settings submenu helps to ensure that the end of probe signal within the envelope curve is correctly assigned by the evaluation algorithm. The assignment is correct if the length of probe indicated by the device matches the acutal lenght of the probe. The automatic probe length correction can only be performed if the probe is installed in the vessel and is completely uncovered (no medium).
Page 147
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu Confirm probe length Navigation Setup → Advanced setup → Probe settings → Confirm length Description Select, whether the value displayed in the Present probe length parameter → 146 matches the actual length of the probe. Based on this input, the device performs a probe length correction.
Page 148
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA "Probe length correction" wizard The Probe length correction wizard is only available when operating via the local display. When operating via an operating tool, all parameters concerning the probe length correction are located directly in the Probe settings submenu (→ 146).
Page 149
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu "Switch output" submenu Navigation Setup → Advanced setup → Switch output Switch output function Navigation Setup → Advanced setup → Switch output → Switch out funct Description Select function for switch output.
Page 150
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA • Digital output 2 • Digital output 3 • Digital output 4 Factory setting Additional information The Digital output AD 1 and Digital output AD 2 options refer to the Advanced Diagnostic Blocks. A switch signal generated in these blocks can be transmitted via the switch output.
Page 151
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu Switch-on value Navigation Setup → Advanced setup → Switch output → Switch-on value Prerequisite Switch output function (→ 149) = Limit Description Enter measured value for the switch-on point. User entry...
Page 154
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA Additional information Meaning of the options • No The behavior of the switch output is as described above. • Yes The states Open and Closed are inverted as compared to the description above.
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu "Display" submenu The Display submenu is only visible if a display module is connected to the device. Navigation Setup → Advanced setup → Display Language Navigation Setup → Advanced setup → Display → Language Description Set display language.
Page 156
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA Additional information 4841.000 Â A0019963 38 "Format display" = "1 value, max. size" Â 93.5 % Â 159.0 A0019964 39 "Format display" = "1 bargraph + 1 value" Â 93.5 Â...
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu Value 1 to 4 display Navigation Setup → Advanced setup → Display → Value 1 display Description Select the measured value that is shown on the local display. Selection • None •...
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA Factory setting Additional information This parameter is only relevant if the number of selected measuring values exceeds the number of values the selected display format can display simultaneously. Display damping Navigation Setup → Advanced setup → Display → Display damping Description Define display reaction time to fluctuations in the measured value.
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu Description Enter display header text. Factory setting ------------ Additional information The number of characters which can be displayed depends on the characters used. Separator Navigation Setup → Advanced setup → Display → Separator Description Select decimal separator for displaying numerical values.
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA Additional information • Is only valid for numbers in the operating menu (e.g. Empty calibration, Full calibration), but not for the measured value display. The number of decimal places for the measured value display is defined in the Decimal places 1 to 4 → 157 parameters.
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu "Configuration backup display" submenu This submenu is only visible if a display module is connected to the device. The configuration of the device can be saved to the display module at a certain point of time (backup).
Page 162
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA Additional information Meaning of the options • Cancel No action is executed and the user exits the parameter. • Execute backup A backup copy of the current device configuration in the HistoROM (built-in in the device) is saved to the display module of the device.
Page 163
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu Additional information Meaning of the display options • Settings identical The current device configuration of the HistoROM is identical to the backup copy in the display module. • Settings not identical The current device configuration of the HistoROM is not identical to the backup copy in the display module.
Page 164
Enter access code parameter (→ 125). Please contact your Endress+Hauser Sales Center if you lose your access code. For display operation: The new access code is only valid after it has been confirmed in the Confirm access code parameter (→...
Page 165
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu Additional information Meaning of the options • Cancel No action • To factory defaults All parameters are reset to the order-code specific factory setting. • To delivery settings All parameters are reset to the delivery setting. The delivery setting may differ from the factory default if customer specific settings have been ordered.
Page 166
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA "Define access code" wizard The Define access code wizard is only available when operating via the local display. When operating via an operating tool, the Define access code parameter is located directly in the Administration submenu. The Confirm access code parameter is not available for operation via operating tool.
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu 16.4 "Diagnostics" menu Navigation Diagnostics Actual diagnostics Navigation Diagnostics → Actual diagnos. Description Displays current diagnostic message. Additional information The display consists of: • Symbol for event behavior • Code for diagnostic behavior •...
Page 168
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA Timestamp Navigation Diagnostics → Timestamp Description Displays timestamp for the Previous diagnostics parameter (→ 167). User interface Days (d), hours (h), minutes (m), seconds (s) Operating time from restart Navigation Diagnostics → Time fr. restart Description Displays the time the device has been in operation since the last device restart.
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu 16.4.1 "Diagnostic list" submenu Navigation Diagnostics → Diagnostic list Diagnostics 1 to 5 Navigation Diagnostics → Diagnostic list → Diagnostics 1 to 5 Description Display the current diagnostics messages with the highest to fifth-highest priority.
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA 16.4.2 "Event logbook" submenu The Event logbook submenu is only available when operating via the local display. When operating via FieldCare, the event list can be displayed in the FieldCare function "Event List / HistoROM".
Displays serial number of the device. Additional information Uses of the serial number • To identify the device quickly, e.g. when contacting Endress+Hauser. • To obtain specific information on the device using the Device Viewer: www.endress.com/deviceviewer The serial number is also indicated on the nameplate.
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA Order code Navigation Diagnostics → Device info → Order code Description Displays order code of the device. Additional information The order code is generated from the extended roder code, which defines all device features of the product structure.
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu 16.4.4 "Measured values" submenu Navigation Diagnostics → Measured val. Distance Navigation Diagnostics → Measured val. → Distance Description Displays the measured distance D between the reference point (lower edge of the flange or threaded connection) and the level.
Page 174
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA Switch status Navigation Diagnostics → Measured val. → Switch status Description Displays the current state of the switch output. Endress+Hauser...
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu 16.4.5 "Analog input 1 to 6" submenu There is an Analog input submenu for each Analog Input Block of the device. Only the most important parameters of the respective block are available at this position of the operating menu.
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA Factory setting Additional information • For Mode block actual = Man: Enter the output value of the Analog Input Block. • Else: Displays the output value of the Analog Input Block. Out status Navigation ...
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu 16.4.6 "Data logging" submenu Navigation Diagnostics → Data logging Assign channel 1 to 4 Navigation Diagnostics → Data logging → Assign chan. 1 to 4 Description Allocate a process variable to the respective data logging channel.
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA Logging interval Navigation Diagnostics → Data logging → Logging interval Description Define logging interval t User entry 1.0 to 3 600.0 s Factory setting 30.0 s Additional information This parameter defines the interval between the individual data points in the data log, and thus the maximum loggable process time T •...
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu "Display channel 1 to 4" submenu The Display channel 1 to 4 submenus are only available for operation via the local display. When operating via FieldCare, the logging diagram can be displayed in the FieldCare function "Event List / HistoROM"...
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA 16.4.7 "Simulation" submenu The Simulation submenu is used to simulate specific measuring values or other conditions. This helps to check the correct configuration of the device and connected control units. Conditions which can be simulated...
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu Selection • Off • On Factory setting Switch status Navigation Expert → Diagnostics → Simulation → Switch status Prerequisite Switch output simulation (→ 182) = On Description Define the switch state to be simulated.
Page 184
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA Additional information When operated via the local display, the selection list can be filtered according to the event categories (Diagnostic event category parameter). Endress+Hauser...
Page 186
Operating menu Levelflex FMP56, FMP57 PROFIBUS PA Level signal Navigation Diagnostics → Device check → Level signal Prerequisite Device check has been performed. Description Displays result of the device check for the level signal. User interface • Check not done •...
Levelflex FMP56, FMP57 PROFIBUS PA Operating menu 16.4.9 "Heartbeat" submenu The Heartbeat submenu is only available via FieldCare or DeviceCare. It contains the wizards which are part of the Heartbeat Verification and Heartbeat Monitoring application packages. Detailed description SD01872F Navigation ...