Appendix A: Network Points List for RTU Open

Network points list for BACnet and Modbus

Point Name
Point
Access
SA Vent / Temper
R/W
Setpoint
VFD Speed Config
R/W
Heating VFD Output
R/W
Voltage Used to Set IDF
R/W
VFD Heat Speed
Voltage Used to Set IDF
R/W
VFD Maximum Speed
Voltage Used to Set IDF
R/W
VFD Minimum Speed
Tempering Enable
R/W
VFD Speed Test
R/W
Supply Fan VFD Voltage
R
VFD Analog Input
R/W
Channel Type
Active Heat Stages
R
Effective Cool Setpoint
R
High Space Temperature R
Low Space Temperature R
Input_6
R
Supply Fan Relay State
R
Supply Fan Status
R
Economizer Output
R
Outdoor Air Quality
R
Sensor
DCV Max Vent Damper
R/W
Pos
Space Temperature -
R
Prime Variable
HP Rev Cycle Lockout
R/W
Temp
System Outdoor Air
R/W
Temperature
Economizer Purge Min
R/W
Pos
Active Compressor
R
Stages
System Mode
R
RTU Open v5
Integration Guide
Units
Default
Value
°F
65
%/V
%
%
100
V
4.4
V
10
V
5.2
Disable
V
0
V
Vdc
2 to 10
°F
0=Normal
1=Alarm
0=Normal
1=Alarm
°F
0=Off
1=On
0=Off
1=On
%Open
0=Normal
1=Alarm
%Open
50
°F
°F
-3
°F
-999
%Open
40
1=Off
2=Fan Only
3=Economizer
Cooling
4=Cooling
5=Heating
6=Dehumidificati
44
BACnet
BACnet Point Name
BACnet
Object ID
tempering_stpt
AV:3032
vfd_spd_cfg
AV:1030
heat_vfd_spd
AV:3033
ht_spd_volt
AV:83010
max_spd_volt
AV:83011
min_spd_volt
AV:83012
sa_tempering_en
AV:83016
vfd_spdv_test
AV:81003
vfd_volt_output
AV:2032
vfd_in_type
AV:91010
heat_run
AV:2003
eff_cl_stpt
AV:3005
spt_hi_alarm
BV:7011
spt_lo_alarm
BV:7012
ai_6
AI:1006
sfan
BV:2001
sfan_status
BV:1003
econ_output
AV:2022
oaq_fail
BV:7006
iaq_dpr_max
AV:9011
space_temp
AV:2007
hp_rev_cycle_lockout
AV:9004
system_oat
AV:1901
econ_purge_min
AV:9029
comp_run
AV:2020
run_status
MSV:2002
Modbus
Modbus Register
Modbus
Type
Register #
Holding Register
174
(Float)
Input Register
33
(Float)
Input Register
55
(Float)
Discrete Input
35
Discrete Input
39
Discrete Input
23
Discrete Input
24
Input Register
51
(Float)
Discrete Input
41
Holding Register
47
(Float)
Input Register
107
(Float)
Holding Register
71
(Float)
Holding Register
119
(Float)
Holding Register
75
(Float)
Input Register
31
(Float)
Input Register
1
(Signed)
CARRIER CORPORATION ©2019