6.2.15. Gas pipe tests

Calling up the function:

6.2.15.1. Leakage rate test

> Connect the connecting plug of the hose pressure connection
set (0554 1203) to the pressure test set (0554 1213), plug the
pressure adapter onto the flue gas socket and lock in place by
slightly turning it clockwise (bayonet lock).
→ Clipboard: Data are saved to the clipboard.
clipboard: Any data saved to the clipboard
→ Save: The meas. views are saved in a protocol.
Adapter
→ Identification: Information about manufacturer
→ Statistics: Display of failure statistics.
Automatic stokers are equipped with a circular buffer
memory: Error messages are overwritten when the error log
is full. The fault that has occurred last is at position 1 in the
error list.
→ Fault: Display of faults.
Leakproof test on gas pipes acc. to DVGW-TRGI 2008
worksheet G600
The leakproof test (using air or inert gas, e.g. CO2 or N2) is
used for acceptance testing of newly routed or remedied
pipes. The test is performed at the pipe, including the
fittings, without gas installations and corresponding control
and safety equipment. For this test the line must be
pressurized with 150 mbar, whereby this pressure must
remain constant for 10 minutes.
This applies to lines < 100 l. For larger line volumes, the
stability time and measurement period should be adjusted
in accordance with DVGW-TRGI 2008 worksheet G600.