3. MAINTENANCE MENUS

The Maintenance Menus are accessible after entering a Maintenance access code (default 2222).
Maintenance Menus
Silence buzzer
Silence Sounders
Reset
Evacuation
Test
View history LOG
Zones
Devices Setup
Panel outputs
General Settings:
Time/ Day
Day/ Night alarm mode Reviewing of the set Day/ Night alarm mode.
Panel settings
Delay Т1
Sounders mode
Company logo
Save configuration
Software revision
Active isolators
Access level 1

3.1. View History Log Menu

This menu allows the technician to review and print the system events recorded in the panel memory log file. The
capacity of the panel memory log file is 10000 events.
After entering the menu, the screen displays:
Deactivating Internal Buzzer.
Deactivating the Sounders.
During active fire alarms and deactivated/ silenced sounders the LED next the button is
lighting up.
Resetting the panel without switching off the main and backup power supplies.
Activating Evacuation alarm signal; the sounders will activate immediately overriding all
introduced delays.
General test for operability of all LEDs and internal buzzer.
Viewing the LOG file for all events; printing of all or separate events.
Reviewing the Zone status; zone test for operability, disablement.
Reviewing the Device status; disablement.
Disablement of built-in panel outputs: SOUNDERS, EXITING, FIRE, FAULT, RELAY
OUTPUTS.
General settings common for the panel.
Setting the current time and date.
Changing the menu language, setting the backlight brightness; entering disablements.
Setting the Delay Т1.
Reviewing of the set operation of SOUNDER outputs.
Enter company information for the main screen
Saving the set system configuration.
Reviewing the current software revision.
Reviewing the activated isolators in the system.
Return to Access Level 1.
The following general information is displayed in the main screen of
VIEW LOG menu:
Total Entries - Shows the total number of the recorded events in the
memory log file.
Total Alarms Count - Shows the total number of the registered alarm
events.
Use the functional digit buttons to enter the respective submenu.