Observation - Endress+Hauser Liquiphant FTL31 IO-Link Operating Instructions Manual

Point level switch for liquids
Hide thumbs Also See for Liquiphant FTL31 IO-Link:
Table of Contents

Advertisement

Liquiphant FTL31 IO-Link
Navigation
Description
Note
Device Access Locks.Data Storage Lock
1)
The "Device Access Locks.Data Storage Lock" parameter is an IO-Link standard parameter. The name of the
parameter may exist in the configured language in the IO-Link operating tool used. The display depends on the
operating tool in question.
Navigation
Description
Options
15.3

Observation

The process data are transmitted acyclically.
Endress+Hauser
Parameter → System → Standard Command
WARNING
L
"Standard Command" cause an immediate reset to the
factory setting when the device was delivered.
If the factory settings have been changed, downstream
processes might be affected following a reset (the behavior
of the switch output or current output might be changed).
Make sure that downstream processes are not started
unintentionally.
The reset is not subject to additional locking, such as in the
form of device locking. The reset also depends on the device
status.
Any customer-specific configuration carried out at the
factory is not affected by a reset (customer-specific
configuration remains).
The last error is not reset in a reset.
1)
Activation/deactivation of DataStorage
Parameter → System → Device Access Locks.Data Storage
Lock
The device supports DataStorage. If a device is being
replaced, this allows the configuration of the old device to
be written to the new device. If, when a device is being
replaced, the original configuration of the new device is to
be retained, the Device Access Locks.Data Storage Lock
parameter can be used to prevent the parameters from
being overwritten. If this parameter is set to "true", the new
device does not adopt the data stored in the master' s
DataStorage.
• false
• true
Description of device parameters
49