Description
Endress+Hauser
Parameter → Application → Output Switch 1/2 → Switching
delay time, Output 1/2 (dS1/dS2)
Parameter → Application → Output Switch 1/2 →
Switchback delay time, Output 1/2 (dR1/dR2)
The switching delay time/switchback delay time functions
are implemented using the "dS1"/"dS2" and "dR1"/dR2"
parameters. Since the parameter settings depend on one
another, the parameters are described all together.
• dS1 = switching delay time, output 1
• dS2 = switching delay time, output 2
• dR1 = switchback delay time, output 1
• dR2 = switchback delay time, output 2
Set the delay:
To prevent rapid switching back and forth when values are
close to the switch point "SP1"/"SP2" or switchback point
"rP1"/"rP2", a delay in the range of 0.3 to 60 seconds, to one
decimal place, can be set for individual points.
If the measured value leaves the switching range during the
delay time, the delay time starts again.