Diagnostics and troubleshooting

Troubleshooting: If an electronic/sensor defect is present, the device changes to error
mode and displays the diagnostic event F270. The status of the process data is rendered
invalid. The switch output(s) is/are opened.
12.1

General troubleshooting

Device not responding
Supply voltage does not match the value indicated on the nameplate.
Connect the correct voltage.
Supply voltage has incorrect polarity.
Correct the polarity.
Connecting cables are not in contact with the terminals.
Check for electrical contact between cables and correct.
No communication
Communication cable not connected.
Check wiring and cables.
Communication cable incorrectly attached to device.
Check wiring and cables.
Communication cable incorrectly attached to the IO-Link master.
Check wiring and cables.
No transmission of process data
An error has occurred in the device, e.g. internal sensor error or electronics error.
Correct all errors that are displayed as a diagnostic event .
12.2
Diagnostic information via LED indicator
LED indicator on housing cover
Green LED not lit
No supply voltage.
Check plug, cable and supply voltage.
LED flashing red
Overload or short-circuit in load circuit.
Rectify short-circuit.
Reduce maximum load current to below 200 mA if one switch output is active.
Maximum load current = 105 mA per output if both switch outputs are active.
Ambient temperature outside of specification.
Operate measuring device in specified temperature range.
Test magnet held against marking for too long.
Repeat function test.