Electrical connection
Maximum safety
Terminal assignment
2 1
3 4
K1
L–
Function monitoring with M12 plug
When both outputs are connected, the MIN and MAX outputs assume opposite states (XOR)
when the device is operating fault-free. In the event of an alarm condition or a line break,
both outputs are de-energized. This means that function monitoring is possible in addition to
level monitoring. The behavior of the switch outputs can be configured via IO-Link.
Connection for function monitoring using XOR operation
Terminal assignment
2 1
3 4
0.5A
K1
K2
L–
L+
6.4
Post-connection check
Are the device and cable undamaged (visual inspection)?
Does the supply voltage match the specifications on the nameplate?
If supply voltage is present, is the green LED lit?
With IO-Link communication: is the green LED flashing?
20
0.5A
L+
MAX output
ye2
+
2
+
2
+
2
MAX output
+
+
LED yellow
MIN output
(ye) 2
A0037918
Liquiphant FTL31 IO-Link
LED yellow (ye) 2
ye2
2
2
LED
yellow
(ye) 1
ye1
A0037919
+
4
+
4
+
4
Endress+Hauser
A0037918
LED red
(rd)