Operation; Reading Off The Device Locking Status; Reading Off Measured Values; Adapting The Device To Process Conditions - Endress+Hauser Liquiphant FTL51B Operating Instructions Manual

Vibronic hart point level switch for liquids
Hide thumbs Also See for Liquiphant FTL51B:
Table of Contents

Advertisement

Operation

36
Parameter configuration (Operator user role):
Parameter configuration of the device is locked in the Operator user role.
Unlocking access:
Access to parameter configuration can be unlocked by entering the password. The user
role changes back to Maintenance.
Navigation for assigning the password and changing the user role: System → User
management
Delete password:
If necessary, the password can be deleted in the User management.
Navigation: System → User management → Delete password → Start
10
Operation
10.1

Reading off the device locking status

Displaying active write protection in the Locking status parameter
• Local display  :
The
symbol appears on the main page
• Operating tool (FieldCare/DeviceCare)  :
Navigation: System → Device management → Locking status
10.2

Reading off measured values

All the measured values can be read off using the Measured values submenu.
Navigation: Application menu → Measured values submenu
10.3

Adapting the device to process conditions

The following menus are available for this purpose:
• Basic settings in the Guidance menu
• Advanced settings in:
• Diagnostics menu
• Application menu
• System menu
10.3.1

Level limit detection

Operating as a point level switch in the 8/16 mA mode.
Output of point level:
• 8 mA (demand mode: MIN uncovered or MAX covered)
• 16 mA (OK status: MIN covered or MAX uncovered)
1. Navigation: Application → Sensor → Sensor configuration
2. Set the Mode of operation to Level limit detection.
3. Set the Safety function to MIN (dry-running prevention) or MAX (overfill protection),
according to the application.
4. Set the Density setting parameter according to the application (> 0.4 g/cm³, > 0.5 g/
cm³, > 0.7 g/cm³ ).
5. Optionally: Set the Switching delay uncovered to covered parameter and the
Switching delay covered to uncovered parameter.
Liquiphant FTL51B HART
Endress+Hauser

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hart liquiphant ftl51b

Table of Contents