Liquiphant FTL31 IO-Link
7

Operation options

7.1

Operation with operating menu

7.1.1
IO-Link information
IO-Link is a point-to-point connection for communication between the measuring device and
an IO-Link master. The measuring device features an IO-Link communication interface type 2
with a second IO function on pin 4. This requires an IO-Link-compatible assembly (IO-Link
master) for operation. The IO-Link communication interface enables direct access to the
process and diagnostic data. It also provides the option of configuring the measuring device
while in operation.
Physical properties of the IO-Link interface:
• IO-Link specification: version 1.1
• IO-Link Smart Sensor Profile 2nd Edition
• SIO mode: Yes
• Speed: COM2; 38.4 kBaud
• Minimum cycle time: 6 ms
• Process data width: 16 bit
• IO-Link data storage: Yes
• Block configuration: Yes
• Device operational: The measuring device is operational 1 s after the supply voltage has
been applied
7.1.2
IO-Link download
http://www.endress.com/download
• Select "Software" as the media type
• Select "Device Driver" as the software type
Select IO-Link (IODD)
• In the "Text Search" field enter the device name.
https://ioddfinder.io-link.com/
Search by
• Manufacturer
• Article number
• Product type
7.1.3
Structure of the operating menu
The menu structure has been implemented according to VDMA 24574-1 and complemented
by Endress+Hauser-specific menu items.
  → "Overview of the operating menu" section.
A
1)
Supports minimum scope of IdentClass
Endress+Hauser
1)
Operation options
21