Parameter

15.2.1
Application
Active switchpoints
Navigation
Description
Switch-on value
Selection
Endress+Hauser
On the metal housing cover (IP69), there is no external
signaling via LEDs.
• Off
• On
The function is deactivated after the device is
restarted.
Off
Diagnosis → Sensor check
This parameter is used to test if the measuring point is
functioning correctly.
The sensor must not be covered and must be free of residue.
The device compares the current measured values with the
measured values from the factory adjustment.
Check: Following the test, one of the following messages is
displayed:
• Message (0x1814) for sensor check passed
• Message C103 (0x1813) for sensor check failed
Parameter → Application → Active switchpoints
Choice between standard (0.7 g/cm
customer-specific, user-definable switch points
Last setting selected prior to switching off device.
• Standard
• User
Description of device parameters
3
, 0.5 g/cm
3
) or
41