Rosemount 5600 Series
ANALOG INPUT (AI)
FUNCTION BLOCK
Table 6-7. AI BLOCK_ERR
Conditions
6-6
This section describes error conditions that are supported by the AI Block.
Read Table 6-8 to determine the appropriate corrective action.
.
Condition
Number
Condition Name and Description
0
Other
1
Block Configuration Error: the selected channel carries a measurement that
is incompatible with the engineering units selected in XD_SCALE, the L_TYPE
parameter is not configured, or CHANNEL = zero
3
Simulate Active: Simulation is enabled and the block is using a simulated
value in its execution
7
Input Failure/Process Variable has Bad Status: The hardware is bad, or a
bad status is being simulated
14
Power Up
15
Out of Service: The actual mode is out of service