Solution #3.2; Configuration Using The Sensor Bus Port; Electrical Connection - Emerson Rosemount 5600 Series Reference Manual

Radar level transmitter with foundation fieldbus protocol
Hide thumbs Also See for Rosemount 5600 Series:
Table of Contents

Advertisement

Reference Manual
00809-00100-4025, Rev AA
May 2003
Table 4-11. Analog Input
Function Block Configuration for
a Radar Level Transmitter used
in Level Measurement
(Situation #3)
Figure 4-10. Function Block
Diagram for a Level Transmitter
where level output is sealed
between 0-100%
CONFIGURATION USING
THE SENSOR BUS PORT

Electrical Connection

Solution #3.2

In this solution the level channel in the analog input block is used to obtain the
volume.
Parameter
L_TYPE
XD_SCALE
OUT_SCALE
Channel
Level
Measurement
When using a 5601 with F
transmitter is done via DeltaV or other Fieldbus Host. With the help of Device
descriptors these hosts are able to present, read, and write necessary
information and data within the transmitter and assist the user to a successful
configuration of the transmitter.
In some cases, there could be a need for a more advanced service access to
the transmitter. This is done by using the Radar Master and accessing the
data from the Sensor Bus Port, which is always readily available. Below are
instructions of how to connect this port and how to use it.
The electrical interface is RS-485 (2-wire) and the language spoken (protocol)
is Modbus.
To be able to connect to the Sensor Bus on the Rosemount 5601, you must
have a RS-232/485 converter. Below you find two models of such
RS-232/485 modems which have been successfully used to communicate
with the 5601 on the Sensor Bus. Basically any type of RS-232/485 converter
can be used but different Models use different switches/settings etc., and
therefore they are not listed here. The recommended type for field use is the
K2.
The converter is to be connected on the Sensor Bus Port which is normally
used by the Rosemount 2210 Display Unit. Disconnect the communication
wires (X2: 6 & 7) to the Display Unit.
Rosemount 5600 Series
AI
OUT_D
Function
Block
OUT
Fieldbus the configuration of the
OUNDATION
Configured Values
Indirect
0 to 14m
3
0 to 200m
1 Level
3
0 to 200m
4-11