Emerson Rosemount 5600 Series Reference Manual page 78

Radar level transmitter with foundation fieldbus protocol
Hide thumbs Also See for Rosemount 5600 Series:
Table of Contents

Advertisement

Reference Manual
00809-0100-4025, Rev AA
May 2003
Index
Parameter
Number
MODE_BLK
05
OUT
08
OUT_D
37
OUT_SCALE
11
PV
07
PV_FTIME
18
SIMULATE
09
STRATEGY
03
ST_REV
01
TAG_DESC
02
UPDATE_EVT
20
VAR_INDEX
39
VAR_SCAN
40
XD_SCALE
10
SIMULATION
Units
Description
None
The actual, target, permitted, and normal modes of the block.
Target: The mode to "go to"
Actual: The mode the "block is currently in"
Permitted: Allowed modes that target may take on
Normal: Most common mode for target
EU of OUT_SCALE
The block output value and status.
None
Discrete output to indicate a selected alarm condition.
None
The high and low scale values, engineering units code, and number of digits to the
right of the decimal point associated with OUT.
EU of XD_SCALE
The process variable used in block execution.
Seconds
The time constant of the first-order PV filter. It is the time required for a 63% change
in the IN value.
None
A group of data that contains the current transducer value and status, the simulated
transducer value and status, and the enable/disable bit.
None
The strategy field can be used to identify grouping of blocks. This data is not
checked or processed by the block.
None
The revision level of the static data associated with the function block. The revision
value will be incremented each time a static parameter value in the block is
changed.
None
The user description of the intended application of the block.
None
This alert is generated by any change to the static data.
% of OUT Range
The average absolute error between the PV and its previous mean value over that
evaluation time defined by VAR_SCAN.
Seconds
The time over which the VAR_INDEX is evaluated.
None
The high and low scale values, engineering units code, and number of digits to the
right of the decimal point associated with the channel input value.
To support testing, you can either change the mode of the block to manual
and adjust the output value, or you can enable simulation through the
configuration tool and manually enter a value for the measurement value and
its status. In both cases, you must first set the ENABLE jumper on the field
device.
NOTE
All fieldbus instruments have a simulation jumper. As a safety measure, the
jumper has to be reset every time there is a power interruption. This measure
is to prevent devices that went through simulation in the staging process from
being installed with simulation enabled.
With simulation enabled, the actual measurement value has no impact on the
OUT value or the status.
Rosemount 5600 Series
E-3