Gear Stage Of The Reduction Gearing: Test/Set - AUMA SA 07.2 Operation Manual

Multi-turn actuators
Hide thumbs Also See for SA 07.2:
Table of Contents

Advertisement

SA 07.2
SA 16.2 / SAR 07.2
AC 01.2 Non-Intrusive DeviceNet
11.2.2.

Gear stage of the reduction gearing: test/set

SAR 16.2 Control unit: electronic (MWG)
4.
Check settings:
The setting of the mechanical position indicator is correct if the angle between
the symbols
(OPEN) and
280°.
If all three discs are turned at the same time, the indicator can be shifted in
steps of 15°. Individual shifts of 5° are possible.
If the indicator is rotated too far (more than 280°) or if the angle is too small
(below 120°), adapt the gear stage setting to the actuator turns/stroke. Refer
to <Gear stage of the reduction gearing: test/set>.
The test/setting is only required if the mechanical position indicator cannot be correctly
set.
1.
Refer to table and check if turns/stroke correspond to the setting of the reduction
gearing (stages 1 9).
Table 30:
Turns of actuator per valve stroke and suitable reduction gearing setting
for 1
500 turns/stroke
[exceeding
to]
1.0
1.9
1.9
3.7
3.7
7.9
7.9
15.0
15.0
31.5
31.5
60.0
60.0
126
126
240
240
500
2.
To modify settings, lift the lever at the reduction gearing and engage at the se-
lected stage.
Figure 79: Set reduction gearing
Commissioning (settings/options in the actuator)
(CLOSED) ranges between approx. 120° and
for 10
5,000 turns/stroke
[exceeding
to]
10
19
19
37
37
79
79
150
150
315
315
600
600
1,260
1,260
2,400
2,400
5,000
Reduction gearing
Stage
1
2
3
4
5
6
7
8
9
77

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sa 16.2Sar 07.2Sar 16.2

Table of Contents