AUMA SA 07.2 Operation Manual page 79

Multi-turn actuators
Hide thumbs Also See for SA 07.2:
Table of Contents

Advertisement

SA 07.2
SA 16.2 / SAR 07.2
AC 01.2 Non-Intrusive DeviceNet
SAR 16.2 Control unit: electronic (MWG)
1.
Pull off indicator disc using a spanner as lever if required.
2.
Refer to table and check if turns/stroke of the actuator correspond to the setting
of the reduction gearing (stages 1 9).
If the setting is not correct: continue with step 3.
If the setting is correct: continue with step 6.
Table 31:
MS5.2 control unit (1 to 500 turns per stroke)
Turns/stroke above
to
1.0
1.9
1.9
3.9
3.9
7.8
7.8
15.6
15.6
31.5
31.5
62.5
62.5
125
125
250
250
500
Table 32:
MS50.2 control unit (10 to 5,000 turns per stroke)
Turns/stroke above
to
10.0
19.5
19.5
39.0
39.0
78.0
78
156
156
315
315
625
625
1,250
1,250
2,500
2,500
5,000
3.
Loosen screw [1].
4.
Set crown wheel [2] to desired stage according to table.
5.
Tighten screw [1].
6.
Place indicator disc on shaft.
7.
Set mechanical position indicator.
Commissioning (settings/options in the actuator)
Gear stage
1
2
3
4
5
6
7
8
9
Gear stage
1
2
3
4
5
6
7
8
9
79