SA 07.2
SA 16.2 / SAR 07.2
AC 01.2 Non-Intrusive DeviceNet
Not ready REMOTE and Function check (collective signal 04)
Indication on display
EMCY behav. active
I/O interface
Handwheel active
FailState fieldbus
Local STOP
Interlock
Interlock by-pass
PVST active
1)
SIL function active
1)
For actuators controls in SIL version
12.3.

Fuses

12.3.1.

Fuses within the actuator controls

F1/F2
F3
F4
F5
SAR 16.2 Control unit: electronic (MWG)
Description/cause
Operation mode EMERGENCY is active (EMER-
GENCY signal was sent).
0 V are applied at the EMERGENCY input.
The actuator is controlled via the I/O interface (par-
allel).
Manual operation is activated.
Fieldbus connection available, however no process
data transmission by the master.
A local STOP is active.
Push button STOP of local controls is operated.
An interlock is active.
By-pass function is interlocked.
Partial Valve Stroke Test (PVST) is active.
SIL function is active
Table 38:
Primary fuses F1/F2 (for power supply unit)
G fuse
Size
Reversing contactors
Power supply ≤ 500 V
Reversing contactors
Power supply > 500 V
Thyristor units for motor power up to 1.5 kW
Thyristor units for motor power up to 3.0 kW
Thyristor units for motor power up to 5.5 kW
Internal 24 V DC supply
Table 39:
Secondary fuses F3 (internal 24 V DC supply)
G fuse according to IEC 60127-2/III
Size
Voltage output (power supply unit) = 24 V
Voltage output (power supply unit) = 115 V
Table 40:
Secondary fuse F4 (internal AC supply)
G-fuse according to IEC 60127-2/III
Size
Voltage output (power supply unit) = 24 V
Voltage output (power supply unit) = 115 V
1)
Fuse for: Switch compartment heater, reversing contactor control, PTC tripping device (at 24 V AC
only), at 115 V AC also control inputs OPEN, STOP, CLOSE
Automatic reset fuse as short-circuit protection for external 24 V DC supply for
customer (see wiring diagram)
Remedy
Detect cause for EMERGENCY signal.
Verify failure source.
Apply +24 V DC at EMERGENCY input.
Check I/O interface.
Start motor operation.
Verify master configuration
Release push button STOP.
Check interlock signal.
Check states of main and by-pass valve.
Wait until PVST function is complete.
F1/F2
6.3 x 32 mm
1 A T; 500 V
2 A FF; 690 V
1 A T; 500 V
F3
5 x 20 mm
2.0 A T; 250 V
2.0 A T; 250 V
1)
F4
5 x 20 mm
1.25 A T; 250 V
Corrective action
AUMA art. no.
K002.277
K002.665
K002.277
AUMA art. no.
K006.106
K006.106
AUMA art. no.
K001.184
85