Commissioning (settings/options in the actuator)
11.2.
Mechanical position indicator (self-adjusting)
Information
11.2.1.
Mechanical position indicator: set
76
SA 07.2
SA 16.2 / SAR 07.2
Figure 76: Mechanical position indicator (self-adjusting)
The self-adjusting mechanical position indicator shows the valve position by means
of an arrow
. When correctly set, the arrow points to symbol
(CLOSED) in the end positions.
The position indications is housed in the actuator switch compartment. Opening the
switch compartment for manual setting is only necessary if the gear stage setting
must be modified of if the factory settings of predefined end position CLOSED (or
OPEN) must be adapted when commissioning.
1.
Move valve to end position CLOSED.
2.
Push both lower discs with the symbols
each other. The disc with the arrow is thereby
Figure 77: Setting position in CLOSED
3.
Move actuator to end position OPEN.
The arrow
rotates in direction OPEN driving the indicator disc with symbol
(OPEN) until the actuator stops in position OPEN.
Figure 78: Operation in direction OPEN (left) and position OPEN (right)
SAR 16.2 Control unit: electronic (MWG)
AC 01.2 Non-Intrusive DeviceNet
(OPEN) and
(CLOSED) towards
is driven:
(OPEN) or