AUMA SA 07.2 Operation Manual page 96

Multi-turn actuators
Hide thumbs Also See for SA 07.2:
Table of Contents

Advertisement

Technical data
Commands and signals of the fieldbus interface
Process representation output
(command signals)
Process representation input (feed-
back signals)
Process representation input (fault
signals)
Behaviour on loss of communication
1)
Requires position transmitter in actuator
2)
Requires position transmitter in actuator
3)
Requires magnetic limit and torque transmitter (MWG) in actuator
4)
Requires position transmitter in actuator
5)
Requires position transmitter in actuator
General data of fieldbus interface
Communication protocol
Network topology
Transmission medium
Fieldbus interface
Transmission rate/cable length
Number of devices
Bus access
Supported fieldbus functions
Service conditions
Use
Mounting position
Installation altitude
Ambient temperature
Humidity
96
SA 07.2
SA 16.2 / SAR 07.2
OPEN, STOP, CLOSE, position setpoint
End positions OPEN, CLOSED
2)
Actual position value
3)
Actual torque value
Selector switch in position LOCAL/REMOTE
4)
Running indication
(depending on the direction)
Torque switches OPEN, CLOSE
Limit switches OPEN, CLOSED
Manual handwheel operation
2 analogue and 4 digital customer inputs
Motor protection tripped
Torque switch tripped in mid-travel
One phase missing
Failure of analogue customer inputs
DeviceNet communication loss is not detected by the actuator. Appropriate monitoring is recommended
on DCS side.
DeviceNet according to IEC 61158 and IEC 61784-1
Topology with one trunk and optional spurs
DeviceNet power supply and DeviceNet data signals within one cable
Coupling and uncoupling of devices during operation without affecting other devices is possible
Twisted, shielded copper cable with one wire pair for signal transmission and one wire pair for DeviceNet
power supply
Based on the data transmission with CAN telegrams
Baud rate and maximum trunk length:
-
at 125 kbit/s: Thick Cable 500 m, Thin Cable 100 m
-
at 250 kbit/s: Thick Cable 250 m, Thin Cable 100 m
-
at 500 kbit/s: Thick Cable 100 m, Thin Cable 100 m
Baud rate and maximum cumulated spur length:
-
at 125 kbit/s: 156 m
-
at 250 kbit/s: 78 m
-
at 500 kbit/s: 39 m
Baud rate and maximum, single spur length:
-
at 125 kbit/s: 6 m
-
at 250 kbit/s: 6 m
-
at 500 kbit/s: 6 m
Up to 64 DeviceNet devices can be connected
Data exchange as polling
Group 2 only Server
Predifined Master/Slave Connection Set:
-
I/O Poll Connection
Indoor and outdoor use permissible
Any position
≤ 2 000 m above sea level
> 2,000 m above sea level, on request
Refer to name plate of actuator controls
Up to 100 % relative humidity across the entire permissible temperature range
SAR 16.2 Control unit: electronic (MWG)
AC 01.2 Non-Intrusive DeviceNet
1)
, RESET
5)
or local controls