6.21 Replacing a Compensation Module

Prerequisites
When short-circuiting and restoring the terminals of the current transformer, wear
insulated gloves and do not touch conductors.
Procedure
Step 1 Locate the current transformer terminals based on the electrical diagram and
labels. Record and short-circuit the three-phase current transformer terminals.
If the current transformer terminals are not short-circuited before the
compensation module is replaced with power on, the controller will be damaged
and electric shocks may occur.
Figure 6-29 Short-circuiting terminals (1)
Issue 02 (2022-07-18)
NO TE
If the Auto indicator on the ATS is off, press the RESET button on the ATS panel to switch
the ATS control mode to automatic.
D ANGER
Tools: electroprobe, insulated gloves, flat-head screwdriver, lifting trolley
Material: a new and intact compensation module of the same model
D ANGER
Copyright © Huawei Digital Power Technologies Co., Ltd.
6 Component Replacement
65