Maintenance Guide
Step 4 Remove the old PAD from the support and install the new PAD on the support.
Step 5 Connect the charging cable to the new PAD.
----End

6.2 Replacing an ECC800-Pro Main Control Module

Prerequisites
Procedure
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
Step 2 Use the Back Up Current Settings function to record the ECC800-Pro
configuration information or manually record the information.
Path: Maintenance > Configuration File > Back Up Current Settings
● If the main control module is damaged, you may fail to log in to the ECC800-Pro. In this
● The following information cannot be backed up: monitoring module IP address parameters,
Step 3 Mark the corresponding port names on the cables connected to the front and rear
of the ECC800-Pro main control module, and then remove the cables.
Step 4 Remove the WiFi module and antenna from the ECC800-Pro main control module.
Step 5 Loosen the captive screws on the panel of the old ECC800-Pro main control
module, and pull the handle outwards to remove the main control module from
the subrack.
Figure 6-1 Removing the ECC800-Pro main control module
Step 6 (Optional) Remove the SIM card from the corresponding slot of the ECC800-Pro
main control module.
Issue 02 (2022-07-18)
Tools: ESD wrist strap, ESD gloves, Phillips screwdriver, label, marker
Material: a new and intact ECC800-Pro main control module of the same
model
NO TE
case, you cannot back up the settings.
smart module certificate, management system certificate, management system second-
challenge password, time configuration parameters, access user management, access
permission management, device access certificate, log, and user configuration information.
Copyright © Huawei Digital Power Technologies Co., Ltd.