5.2 Replacement of main component
Danger: The PowerCube-M1-C is a high voltage DC system, operated by qualified
and authorized person only.
PowerCube-M1-C est un système à courant continu à haute tension, opéré
uniquement par le personnel qualifié et autorisé.
Danger: Before replace the main component must shut off the maintenance battery string's
power. Must confirm the D+ and D- terminal are without power. The turn off progress
refer to chapter 3.6.5.
5.2.1 Replacement of Battery Module
A new battery module can be add onto an existing system at any time. Please make sure the new
battery module has an equivalent voltage level (OCV) compare to existing modules. In a serial
connection system, the new module, even has a higher SOH, will follow the system worst SOH
condition module to perform.
5.2.1.1 Make sure the new battery module has an equivalent voltage level (OCV) compare to
existing modules.
5.2.1.2 Shut off the whole battery string's power. Must confirm the D+ and D- terminal are without
power. The turn off progress refer to chapter 3.6.5.
5.2.1.3 Pull out the Plug of Power Cable +/-. Pull out the plug of communication cable.
Danger: the power cables and plugs still have high voltage DC power from serial
connected battery modules (battery module can't be turned off), must be careful to
handle the Power plugs.
Les câbles d'alimentation et les fiches sont toujours alimentés en courant continu à haute tension
par les modules de batterie connectés en série (le module de batterie ne peut pas être éteint),
vous devez donc manipuler les fiches avec précaution.
5.2.1.4 Dismantle the 4 screws of the battery module's front face.