1)
Turn off the power switch of PCS, to make sure no current through this battery string.
2)
Turn off all the external switches or breaker between PCS and each battery strings.
3)
Turn off the "Isolating Switch" of the BMS.
4)
Turn off the "Power Switch" of the BMS.
5)
Turn off the "Power Switch" of the MBMS. If the ESS configures only single battery without MBMS,
so needn't this operation step.
6)
Turn off the UPS(if has).
The UPS can turn on if have equipment must keep running can't turn off. Otherwise
must turn off the UPS to save its power.
L'UPS peut s'allumer si l'équipement doit continuer à fonctionner et ne peut pas
s'éteindre. Sinon, vous devez éteindre l'UPS pour économiser son énergie.
Caution: Before change the battery module for service, must charge/discharge the
replaced battery same voltage to the other in system battery modules. Otherwise the
system need long time to do the balance for this replaced battery module.
Avant de remplacer le module de batterie pour le service, vous devez charger/décharger la
batterie remplacée à la même tension dans les modules de batterie du système. Sinon, le
système a besoin d'une longue durée pour équilibrer ce module de batterie remplacé.