4.3.13.1 Advanced Controls Build Option
When encountering the Edit Controls interface with the Advanced Controls build option, you'll see an additional
checkbox below the main window titled 'Enable Advanced Features'. These advanced features control the timing
for a generator and are used to charge the batteries. To configure advanced controls settings, select this
checkbox.
NOTE: Selecting the 'Enable Advanced Features' checkbox will occupy control relay slots #1 and #2.
Monitoring Trigger
Generator Warm-Up Time Determines how long the generator will run before Control #2 latches, initiating
Battery Charge Time
Generator Cooldown Time Determines how long the generator will cooldown until Control #1 releases. Can
Once you have configured your settings, press the 'Submit Data' button. In order for the changes to take effect,
you will need to reboot your NetGuardian 420 device.
Edit Controls > Enable Advanced Features
This selects which severity level will cause Control #1 to latch and start the
generator. The Battery Monitoring feature monitors analog channels 5 and/or 6
(Battery A and B).
the battery charging. Can be configured in seconds, minutes or hours, within a
range of 1 - 120.
Determines how long the batteries will charge until Control #2 releases. Can be
configured in seconds, minutes or hours, within a range of 1 - 120.
be configured in seconds, minutes or hours, within a range of 1 - 120.