Q3: How are the local registers mapped to the polled data in a MDC‐700?   
A3: Only the function code 01/02/03/04 can be used in the polling definition section in config.csv file.   
01: Read Coil Status (Read DO) 
02: Read Input Status (Read DI) 
03: Read Holding Registers (Read AO) 
04: Read Input Registers (Read AI) 
 
Refer to the example below,   
#  UseComPort  SlaveModbusID  FunctionCode RegStart 
  2 
    The MDC‐700 will sort the order of polling data by COM port number and the sequence of polling 
definition; and then map the local registers corresponding to the data type (DI/DO/AI/AO) by the 
order of polling data. So the data comes from different slave devices with the same type will be 
saved in continuous registers, and a Modbus mater device and read the data on a variety of slave 
devices with one Modbus command.   
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Copyright © 2014 ICP DAS Co., Ltd. All Rights Reserved.  ∗  E‐mail: service@icpdas.com                                          ‐ 32 ‐ 
COM1 
Read DO: 000000:000007 
Read DI: 100000:100007 
COM2 
Read DO: 000000:000003 
Read DI: 100000:100003 
Read AO: 400000:400003 
Read AI: 300000:300003 
RegCount 
Addr 
1
0
2
0
1
0
2
0
3
0
4
0
Timeout 
Preset 
EventProcess 
Value 
8
8
4
4
4
4
Read DO 
000000:000007 
000008:000011 
Read DI 
100000:100007 
100008:100011 
Read AO 
400000:400003
Read AI 
300000:300003 
0
0
0
0
0
0
 