 Situation #5:
An incorrect ID of the Modbus slave device is being specified.
Solution: Check and fix the difference of ID number between the polling definition and the
slave device.
 Situation #6:
The Timeout or PollDelay setting is not long enough.
Solution: Lengthen the Timeout or PollDelay setting until it is suitable for communication with the
slave device.
ComPortNo
BaudRate
1
2
3
4
5
Copyright © 2014 ICP DAS Co., Ltd. All Rights Reserved. ∗ E-mail: service@icpdas.com
DataBit
Parity
9600
8
0
9600
8
0
9600
8
0
9600
8
0
9600
8
0
StopBit
Timeout
PollDelay
1
120
1
3000
1
3000
1
120
1
120
Operating
Mode
100
Master
1000
Master
1000
Master
100
Master
100
Master
- 46 -