 Power Connector
 Configuration Display
MDC-700 includes a 5-digit 7-Segment LED display to indicate configuration in a module as below:
11111.
1. 192
2. 168
3. 255
4.
1
22222.
502
001
33333.
1.1152
2.1152
44444.
1. 801
2. 801
55555.
00
Copyright © 2014 ICP DAS Co., Ltd. All Rights Reserved. ∗ E-mail: service@icpdas.com
The IP address for the MDC-700
(192.168.255.1)
Modbus TCP communication settings
Port: 502
Net ID: 1
Baud rate setting for each COM port
COM1: 115200 bps
COM2: 115200 bps
Data format setting for each COM port
COM1: 8N1
COM2: 8N1
The count of TCP/IP connection
0: No TCP/IP connection