Q3: How are the local registers mapped to the polled data in a MDC‐700?   
A3: Only the function code 01/02/03/04 can be used in the polling definition section in config.csv file.   
01: Read Coil Status (Read DO) 
02: Read Input Status (Read DI) 
03: Read Holding Registers (Read AO) 
04: Read Input Registers (Read AI) 
 
Refer to the example below,   
UseComPort SlaveModbusID FunctionCode RegStartAddr RegCount
 
     
The MDC‐700 will sort the order of polling data by COM port number and the sequence of 
polling definition; and then map the local registers corresponding to the data type 
(DI/DO/AI/AO) by the order of polling data. So the data comes from different slave devices with 
the same type will be saved in continuous registers, and a Modbus mater device and read the 
data on a variety of slave devices with one Modbus command.   
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Copyright © 2014 ICP DAS Co., Ltd. All Rights Reserved.  ∗  E‐mail: service@icpdas.com                                          ‐ 30 ‐ 
COM1 
Read DO: 00000:00007 
Read DI: 10000:10007 
COM2 
Read DO: 00000:00003 
Read DI: 10000:10003 
Read AO: 40000:40003 
Read AI: 30000:30003 
1
0
2
0
1
0
2
0
3
0
4
0
Read DO 
00000:00007 
00008:00011 
Read DI 
10000:10007 
10008:10011 
Read AO 
40000:40003 
Read AI 
30000:30003 