Q3: How are the local registers mapped to the polled data in a MDC‐700?
A3: Only the function code 01/02/03/04 can be used in the polling definition section in config.csv file.
01: Read Coil Status (Read DO)
02: Read Input Status (Read DI)
03: Read Holding Registers (Read AO)
04: Read Input Registers (Read AI)
Refer to the example below,
UseComPort SlaveModbusID FunctionCode RegStartAddr RegCount
1
1
2
2
2
2
The MDC‐700 will sort the order of polling data by COM port number and the sequence of
polling definition; and then map the local registers corresponding to the data type
(DI/DO/AI/AO) by the order of polling data. So the data comes from different slave devices with
the same type will be saved in continuous registers, and a Modbus mater device and read the
data on a variety of slave devices with one Modbus command.