Mitsubishi Electric MELSEC iQ-R Series User Manual page 254

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Timeslot information
■Timeslot 0 information (Un\G1245440 to Un\1245455)
Cycle start offset (ns, s unit) and cycle end offset (ns, s unit) or other information on timeslot 0 are stored.
Address
Un\G1245440 to Un\G1245441
Un\G1245442
Un\G1245443
Un\G1245444 to Un\G1245445
Un\1245446
Un\G1245447 to Un\G1245451
Un\G1245452
Un\G1245453
Un\G1245454
Un\G1245455
■Timeslot 1 to 7 information (Un\G1245456 to Un\1245567)
Timeslot 1 to 7 information is stored in the same order as Timeslot 0 information.
RX offset/size information
■RX offset/size information (Un\G1245696 to Un\G1246179)
The start number and the number of points of RX for each station are stored.
Address
Un\G1245696 to Un\G1245697
Un\G1245698 to Un\G1245699
Un\G1245700 to Un\G1245701
Un\G1245702 to Un\G1245703
Un\G1246176 to Un\G1246177
Un\G1246178 to Un\G1246179
The buffer memory address for the offset and size of each station number can be calculated using the following formulas:
• Offset buffer memory address = 1245696 + (station No.)  4
• Size buffer memory address = 1245698 + (station No.)  4
APPX
252
Appendix 3 Buffer Memory
Name
Cycle start offset (ns unit)
Cycle start offset (s unit)
System area
Cycle end offset (ns unit)
Cycle end offset (s unit)
System area
VID (VLAN Identifier)
PCP (Priority Code Point)
EtherType
System area
Description
Station No.0 offset
Station No.0 size (in units of words)
Station No.1 offset
Station No.1 size (in units of words)
Station No.120 offset
Station No.120 size (in units of words)
Description
The ns digits of cycle start offset are stored.
Stored range: 0 to 999999999 (ns)
The s digits of cycle start offset are stored.
Stored range: 0 to 65535 (s)
The ns digits of cycle end offset are stored.
Stored range: 0 to 999999999 (ns)
The s digits of cycle end offset are stored.
Stored range: 0 to 65535 (s)
Stores the VID of Timeslot 0.
Storage range: 1 to 4094, 65535 (do not use VID or judge frames to be relayed from VID)
Stores the PCP of Timeslot 0.
Storage range: 0 to 7, 65535 (do not use PCP or judge frames to be relayed from PCP)
Stores the EtherType of the frame to be relayed in Timeslot 0. Timeslot 0 stores 65535.
Storage range: EtherType value of the frame to be relayed, 65535 (Do not judge frames
to be relayed from EtherType)