3.
Check the selected PDO mapping pattern.
4.
Click the [OK] button to close "PDO Mapping Setting".
■Cases where the PDO mapping is not set
The PDO mapping is not set to the target slave stations in the following cases:
• The number of points in "RWr Setting" is one or more points and an entry is not assigned in TPDO.
• The number of points in "RWw Setting" is one or more points and an entry is not assigned in RPDO.
• A line where "Sub-Index" is blank though a value has been entered in "Index" exists.
• Entries are assigned out of the link device range.
• The same entry is assigned to the multiple link devices.
2 PARAMETER SETTINGS
128
2.5 "CC-Link IE TSN Configuration" Window