Dbs Setpoint Values - Johnson Controls FRICK QUANTUM HD Setup

Compressor control panel communications setup
Hide thumbs Also See for FRICK QUANTUM HD:
Table of Contents

Advertisement

090.040-CS (JAN 14)
Page 96
Frick
AB
®
Address
Address
8950
N119:50
8951
N119:51
8952
N119:52
8953
N119:53
8954
N119:54
8955
N119:55
8956
N119:56
8957
N119:57
8958
N119:58
8959
N119:59
8960
N119:60
8961
N119:61
8962
N119:62
8963
N119:63
8964
N119:64
8965
N119:65
8966
N119:66
8967
N119:67
8968
N119:68
8969
N119:69
8970
N119:70
8971
N119:71
8972
N119:72
8973
N119:73
8974
N119:74
8975
N119:75
8976
N119:76
8977
N119:77
8978
N119:78
8979
N119:79
8980
N119:80
8981
N119:81
8982
N119:82
8983
N119:83
8984
N119:84
8985
N119:85
8986
N119:86
8987
N119:87
8988
N119:88
8989
N119:89
8990
N119:90
8991
N119:91
8992
N119:92
8993
N119:93
8994
N119:94
8995
N119:95
8997
N119:97
QUANTUM™ HD COMPRESSOR CONTROL PANEL
COMMUNICATIONS SETUP

DBS SETPOINT VALUES:

Modbus
Read/
Address
Write
48951
R
Average Current
48952
R
Elapsed Run Time Hours
48953
R
Elapsed Run Time Minutes
48954
R
Current Phase A
48955
R
Current Phase B
48956
R
Current Phase C
48957
R
Heatsink Temperature
48958
R
RTD Temperature
48959
R
Thermal Capacity Used
48960
R
Time until Start
48961
R
Full Load Amps
48962
R
Locked Rotor Current
48963
R
Stall Time
48964
R
Jam Current Level
48965
R
Jam Run Delay
48966
R
DBS Service Factor
48967
R
Current Unbalance Alarm Level
48968
R
Current Unbalance Alarm Run Delay
48969
R
RTD Temperature Alarm Level
48970
R
RTD Temperature Trip Level
48971
R
Bypass Time
48972
R
Constant Current Level
48973
R
Ramp Time
48974
R
DBS Version
48975
R
Last Trip Current
48976
R
Last Trip Heatsink Temp
48977
R
Last Trip RTD Temp
48978
R
Last Trip Thermal Capacity
48979
R
Last Trip FLA
48980
R
Last Trip Current Step
48981
R
Last Trip Ramp Time
48982
R
Last Trip Bypass Time
48983
R
Last Run Time Hours
48984
R
Last Run Time Minutes
48985
R
Total Accumulated Run Time Hours
48986
R
Total Accumulated Run Time Minutes
48987
R
Total Number of Starts
48988
R
Total Short Circuit Trips
48989
R
Total Jam Trips
48990
R
Total Phase Loss Trips
48991
R
Total Phase Reversal Trips
48992
R
Total Current Unbalance Trips
48993
R
Total Heatsink Overtemp Trips
48994
R
Total RTD Overtemp Trips
48995
R
Total Thermal Overload Trips
48996
R
Maximum RTD Temperature
48998
R
Locked Rotor Current Setpoint
Description of Data
Units
Amps
Hours
Minutes
Amps
Temperature
Percent (%)
Minutes
Amps
Percent (%)
Seconds
Percent (%)
Seconds
Percent (%)
Seconds
Temperature
Seconds
Percent (%)
Seconds
Real
Amps
Temperature
Percent (%)
Amps
Percent (%)
Seconds
Hours
Minutes
Hours
Minutes
None
Temperature
Percent (%)

Advertisement