Eaton Cutler-Hammer FP 5000 Instruction Leaflet page 72

Protective relay
Hide thumbs Also See for Cutler-Hammer FP 5000:
Table of Contents

Advertisement

System Alarms (continued)
Display Setting
Description
VA Demand
System VA Demand
Alarm
Alarm Setting
Units:
Select units for VA demand
Threshold:
Select magnitude threshold
in primary units
Delay (m):
Select delay time in minutes
Current Demand
System Current Demand
Alarm
Alarm Setting
Pickup:
Select pickup in primary units
Delay (m):
Select delay time in minutes
I THD Alarm
System Current Total Harmonic
Distortion Alarm Setting
Threshold:
Select magnitude of I THD
in primary units
Delay (m):
Select delay time in minutes
V THD Alarm
System Voltage Total Harmonic
Threshold:
Select magnitude of V THD
in primary units
Delay (m):
Select delay time in minutes
Breaker Alarm
Breaker alarm # of operations
& sum of interrupting amps
# of Operation:
# of breaker operations based
on the 52a and 52b contacts
Isum INTR Amp:
Current sum of interrupting
amps measured in kA
Effective Date: 12/05
FP-5000
Setpoint Range/
Value Selection
kVA or MVA
1 to 40,000, Disable
(increments of 1)
0 to 60 minutes
(increments of 1)
10 to 10,000 amps,
Disable (increments of 10)
0 to 60 minutes
(increments of 1)
(Phase CT Primary/100) to
(Phase CT Primary *10)
[increments of Phase CT
Primary/100]
0 to 3600 seconds
(increments of 1s)
Distortion Alarm Setting
Main VTR/10 to
Main VTR *10
(increments of
Main VTR/100)
0 to 3600 seconds
(increments of 1s)
1 to 9999
(increments of 1)
0 to 50,000 kA
2
(increments of 1 kA
For more information visit:
Effective Date: 12/05
2
seconds
2
s)
www.eatonelectrical.com
IL17569C
Page 5-17
Default
Selected
Refer to
Setting
Value
Sec. #
5.5.3
kVA
Disable
0
5.5.3
Disable
0
5.5.3
Disable
0
5.5.3
Disable
0
5.5.3
9999
50,000
Page 5-17